AOP-2 "Excessive Load" Flashcards
1
Q
AOP-2 entry conditions
A
Symptoms of excessive load (PZR pressure/level lowering, audible noise) in conjunction with any of the following:
- EK-0968 “Loop 1 Tave/Tref Gross Deviation” (5 F)
- EK-0969 “Loop 2 Tave/Tref Gross Deviation” (5 F)
- EK-1362 “Containment Pressure Off Normal” (0.8 psi) with a steam leak in containment
- Turbine Governor Valve Control Malfunction (open)
2
Q
AOP-2 automatic actions
A
NONE
3
Q
AOP-2 reactor trip criteria
A
- An un-isolable load rise which exceeds a 1% change in HB Power Steady, NI, or D/T Power (9 MW loss on the generator)
- A plant condition requiring a power reduction at a rate greater than 30%/hr
- EK-1362 “Containment Pressure Off Normal” in alarm AND a steam leak inside containment
- Reactor power greater than or equal to 15% AND Turbine Governor Valve Control in manual and not controlling
4
Q
AOP-2 turbine trip criteria
A
Reactor power less than 15% AND Turbine Governor Valve Control in manual and not controlling
5
Q
AOP-2 immediate actions
A
NONE