AOP-2 "Excessive Load" Flashcards

1
Q

AOP-2 entry conditions

A

Symptoms of excessive load (PZR pressure/level lowering, audible noise) in conjunction with any of the following:

  • EK-0968 “Loop 1 Tave/Tref Gross Deviation” (5 F)
  • EK-0969 “Loop 2 Tave/Tref Gross Deviation” (5 F)
  • EK-1362 “Containment Pressure Off Normal” (0.8 psi) with a steam leak in containment
  • Turbine Governor Valve Control Malfunction (open)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

AOP-2 automatic actions

A

NONE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

AOP-2 reactor trip criteria

A
  • An un-isolable load rise which exceeds a 1% change in HB Power Steady, NI, or D/T Power (9 MW loss on the generator)
  • A plant condition requiring a power reduction at a rate greater than 30%/hr
  • EK-1362 “Containment Pressure Off Normal” in alarm AND a steam leak inside containment
  • Reactor power greater than or equal to 15% AND Turbine Governor Valve Control in manual and not controlling
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

AOP-2 turbine trip criteria

A

Reactor power less than 15% AND Turbine Governor Valve Control in manual and not controlling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

AOP-2 immediate actions

A

NONE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly