AOP-26 "Loss of SFP Cooling" Flashcards
1
Q
AOP-26 entry conditions
A
- EK-1307 “Fuel Pool Clg Pumps P-51A and/or P-51B Trip” AND P-51A or P-51B aligned to spent fuel pool cooling
- EK-1309 “Spent Fuel Pool HI/LO Level” (LO level @ 646’)
- Spent Fuel Pool level lowering as indicated on LI-2141, Channel A SFP Level, or LI-2142, Channel B SFP Level
- TIA_0925_D, “PPC Urgent Alarm, SFP High Temperature” (140 F)
- TIA_0926_D, “PPC Urgent Alarm, SFP North Tilt Pit High Temperature” (140 F)
2
Q
AOP-26 automatic actions
A
NONE
3
Q
AOP-26 reactor trip criteria
A
NONE
4
Q
AOP-26 immediate actions
A
- Place irradiated fuel bundles that are in hoist boxes in 1 of the following locations:
1. bundle’s previous location
2. bundle’s future location
3. tilt machine, then tilt horizontal
4. reactor engineering specified location - Lower SFP Elevator to lower limit
- Move irradiated fuel bundles in Ultrasonic Test Rig or Ultrasonic Fuel Cleaning Rig to their fuel storage rack location