AOP-18 "Loss of Left Train DC Power" Flashcards
1
Q
AOP-18 entry conditions
A
-EK-0548 “125V DC Bus Undervoltage”
AND
-EK-0541 “Battery Chargers Trouble”
AND
-EK-0543 “Preferred AC Bus No 1 Trouble”
AND
-EK-0544 “Preferred AC Bus No 3 Trouble”
2
Q
AOP-18 automatic actions
A
P-8B, Steam Driven Aux Feed Pump, starts
3
Q
AOP-18 reactor trip criteria
A
NONE
4
Q
AOP-18 immediate actions
A
- Verify the reactor tripped, if reset (if not, trip the reactor, if reset)
- Verify the turbine tripped (if not, trip the turbine using PB20AST, HS-0501A, Main Steam from S/G B to close, or manually at the turbine front standard)
- Trip 25F7 and 25H9, Main Generator Output breakers using the jumper