635 Loss Of Cooling Tower Pump (65-EOP-5029) Flashcards

1
Q

OPER - 1.1.1 - IF Colling Tower Pump Tripped
START one of the following Standby Cooling Water Pumps:
- 635P3701
- 635P3702
- 635P3703
- 635P3704

A

OPER - 1.1.2 - Loss of Cooling Tower Pump due to loss of prime, perform the following:

OPER - A - USE local switch or hand wheel to open the 30” MOV discharge valve to ~30% on applicable pump

OPER - B - ENSURE the 3/4” valve on top of the pump is closed

OPER - C - OPEN the 1/2” Raw Water valve to the flush inboard and outboard packing glands.

OPER - D - PRIME pump by performing the following:
1 - OPEN 2” (2) 125 valves between the pump casing
and steam eductor
2 - OPEN 1 1/2” (2) 125 psig steam valves to the steam
eductors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

OPER - E - ONCE the pump has been primed,
START applicable pump motor using the ‘START/STOP’ switch in the Swithgear or outside Hand Switch

  • 635P3702 breaker is located in the 636 Switchgear Room
A

OPER - F - ONCE the pump is running,
OPEN the 3/4” top valve and CLOSE the 1/2” Raw Water valve to the seals

OPER - G - MONITOR the amps on the motor running to full working amps of 401. Make adjustments on discharge valve, if needed, to maintain amps within range

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

CCR - 1.1.3 - Loss of Cooling Tower Pumps due to Loss of steam

A - CONTACT utilities to determine how long the steam outage is expected to last

A

B - NOTIFY First Line Supervisor that the Cooling Tower will be out of service until steam is restored.