635 Loss Of Cooling Tower Pump (65-EOP-5029) Flashcards
OPER - 1.1.1 - IF Colling Tower Pump Tripped
START one of the following Standby Cooling Water Pumps:
- 635P3701
- 635P3702
- 635P3703
- 635P3704
OPER - 1.1.2 - Loss of Cooling Tower Pump due to loss of prime, perform the following:
OPER - A - USE local switch or hand wheel to open the 30” MOV discharge valve to ~30% on applicable pump
OPER - B - ENSURE the 3/4” valve on top of the pump is closed
OPER - C - OPEN the 1/2” Raw Water valve to the flush inboard and outboard packing glands.
OPER - D - PRIME pump by performing the following:
1 - OPEN 2” (2) 125 valves between the pump casing
and steam eductor
2 - OPEN 1 1/2” (2) 125 psig steam valves to the steam
eductors
OPER - E - ONCE the pump has been primed,
START applicable pump motor using the ‘START/STOP’ switch in the Swithgear or outside Hand Switch
- 635P3702 breaker is located in the 636 Switchgear Room
OPER - F - ONCE the pump is running,
OPEN the 3/4” top valve and CLOSE the 1/2” Raw Water valve to the seals
OPER - G - MONITOR the amps on the motor running to full working amps of 401. Make adjustments on discharge valve, if needed, to maintain amps within range
CCR - 1.1.3 - Loss of Cooling Tower Pumps due to Loss of steam
A - CONTACT utilities to determine how long the steam outage is expected to last
B - NOTIFY First Line Supervisor that the Cooling Tower will be out of service until steam is restored.
1.2 - Complete Supplemental Actions