635 Loss of Compressor (65-EOP-5002) Flashcards

1
Q

CCR - 1.1.1 - REDUCE feed rate to minimum once the compressor shuts down

A

CCR - 1.1.2 - ENSURE the 635F0001, Reactor Heater SIS has activated isolating the fuel gas to the burners.
- CLOSE burner isolation valves at the heater

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

CCR/OPER - 1.1.3 - ENSURE permissives and alarms on Hydrogen (H2) Make-Up & Recycle Compressors (635C0001 A/B), are clear:

A

OPER - 1.1.4 - IF the cause of the shutdown can be resolved within 10 minutes of the compressor shutdown
PERFORM the following:

A - CORRECT the issues that caused the compressor shutdown.

B - DECREASE set point on 635 Unit Pressure Controller (65PC0401), by ~40 psig

C - ATTEMPT to START the affected H2 Make-up & Recycle Compressor or START the Spare H2 Make-up & Recycle Compressor in accordance with 65-SOP-2015, Compressor Operation/Maintenance procedure

D - PLACE heater burners back in service

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

CCR/OPER - 1.1.5 - NOTIFY Oil Movements to place 635 into an Off Test Tank

A

OPER - 1.1.6 - IF the cause of the compressor shutdown cannot be resolved within 10 minutes of the compressor shutdown or the compressor will not start, REMOVE the Feed Pump from service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

OPER - 1.1.7 - IF both H2 Make-Up & Recycle Compressors will NOT start, SHUTDOWN 635 Unit in accordance with 65-EOP-5001, Emergency Shutdown Procedure

A

CCR - 1.1.8 - IF H2 Make-Up & Recycle Compressor is in 633 Unit Service, REDUCE rates in 633 Unit as needed until H2 Make-Up & Recycle Compressor is Restarted

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

1.2 Complete Supplemental Actions