634 Loss of Compressor (64-EOP-5002) Flashcards

1
Q

OPER/CCR - 1.1.1 - ESTABLISH radio contact between Console Operator and Outside Operators.

A

OPER - 1.1.2 - NOTIFY the following of loss of the Makeup and Recycle Compressor:
- Shift Supervisor
- Chief Operator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Alert Information
If the Compressor shuts down due to a high liquid level in the suction drum, ENSURE that the suction drum and Compressor case is drained to the minimum, and the issue that caused the high level has been corrected.

A

OPER - 1.1.3 - PERFORM 64-EOP-5001 Emergency Shutdown.
IF the loss of compressor is due to an issue that requires the compressor to be isolated and depressurized

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

REDUCE feed rate to minimum once the compressor shuts down.

A

OPER - 1.1.5 - ENSURE the Heater 634F0001, Reactor Feed Heater SIS has activated automatically isolating the Fuel Gas to the burners or by TRIPPING manually.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

OPER - 1.1.6 - CHECK the Shutdown Summary screen on the PLC for indication of the cause of the shutdown:
- Levels, Pressures, Temps, Seal Leakage, Thrust

A

OPER - 1.1.7 - ATTEMPT to restart the compressor following the steps below:

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

OPER/CCR - A - DETERMINE cause of shutdown and correct

A

OPER - B - PERFORM the following if compressor was shutdown because of high level in one of the Knockout Drums:
1 CORRECT issue that caused the KO drum to fill
2 CHECK compressor case drains for liquid entrapment
3 CHECK the KO drums for high level and drain as needed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

OPER - C - VERIFY that all permissives have been met, and alarms are clear:

A

CCR - D - PLACE 64PC4913, Performance Controller on the Fluid Drive in “MANUAL” @ 0% Output

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

OPER - 1.1.8 - If the cause of the shutdown can be resolved within 10 minutes of the compressor shutdown,
Perform the following:

A

CCR - A - REDUCE 634 Unit pressure to ~730 psig by lowering 64PC0010, Compressor Suction Pressure Controller set point or place 64 PC0010, Compressor Suction Pressure Controller in “MANUAL” mode and slightly open.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

CCR - B - Monitor 634 Unit pressure using 64PC0007, Unit Pressure Controller.

A

OPER - C - PUSH 64HS6412, Hydrogen Compressor Shutdown Reset Button located on the PLC and Bently Nevada to reset the compressor shutdown.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

CCR - D - ENSURE that 64PC4913S, Performance Controller is placed in manual and set at 10%

A

OPER - E - VERIFY the level in the Amine Contactor if they shutdown was due to a high level in 634D0004, Recycle KO Drum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

OPER - F - PUSH 64HS6402A, Hydrogen Compressor Start Button located on the PLC to start the compressor

A

CCR - G - VERIFY <120scfm and >30scfm gas flow to the inboard seal using 64FI6004, Primary Process (H2) Inboard Seal Gas Flow Indicator located on the PLC Dry Gas Seal screen.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

CCR - H - VERIFY <120scfm and >30scfm gas flow to the inboard seal gas using 64FI6005, Primary Process (H2) Outboard Seal Gas Flow Indicators located on the PLC Dry Gas Seal screen

A

OPER - I - CHECK the PLC for any alarms on the compressor and clear as needed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

OPER - J - LISTEN carefully for unusual noises, or vibration. If any of these conditions occur, shut-dow the compressor and notify the Rotating Engineer

A

OPER - K - VERIFY that oil is flowing freely in all sigh glasses, with the exception of the coupling guard drain line

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

CCR - L - INCREASE compressor RPM using the Performance Controller on the Fluid Drive to the lower operating range and place in “AUTO”

A

CCR - M - PLACE the Performance Controller on the Fluid Drive in “MANUAL”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

CCR - N - QUICKLY INCREASE the compressor RPM through the critical speed area (4500 rpm - 8959 rpm) to the upper RPM range

A

CCR - O - PLACE the Performance Controller on the Fluid Drive in “AUTO” and adjust to the desired gas flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

CCR - P - ADJUST 64PC0010, Compressor Pressure Controller to maintain 690-720 psig

A

CCR - Q - RESET 634F001, Reactor Heater SIS and place heater in service

R - INCREASE 634 F0001, Reactor Feed Heater firing rate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

OPER - S - RETURN unit to normal operating temperature and pressure

A

OPER/CCR - 1.1.9 - If the compressor cannot be RESTARTED within 10 minutes of the compressor shutdown.
SHUTDOWN the unit per 64-EOP-5001 Emergency Shutdown

17
Q

OPER - 1.1.10 - NOTIFY the Plant Shift Superintendent that the 634 unit is down and on Nitrogen purge

A

1.2 Complete Supplemental Actions