634 Loss of Heater O2 (64-EOP-5043) Flashcards
CCR/OPER - 1.1.1 - IF outlet temperature on Reactor Feed Heater (634F0001), is not responding to changes in Fuel Gas flow, or Oxygen concentration is less than 1.5% O2 as indicated by Outlet Oxygen Analyzer (64AI0001),
MONITOR Reactor Feed Heater for the following:
CCR - Very low Oxygen (<1.5%) or zero, as indicated by Reactor Feed Heater Stack Analyzer (64AI0001)
CCR - Fuel Gas to heater is increasing and the outlet temperature is decreasing (no change in feed to the heater)
OPER - Stack Smoking
OPER - Abnormal Noise or Rumbling
CCR - Heater coil outlet temperatures are fluctuating with no changes to the other process variables.
CCR - 1.1.2 - IF Emergency Alarm Activates or Oxygen concentration is less than 1.5% O2
PERFORM the following:
CCR - A - REDUCE Fuel Gas pressure to increase Oxygen concentration greater than 1.5% O2
CCR - B - TURN OFF Fuel Gas DMC to prevent inappropriate adjustments to Reactor Feed Heater
CCR/OPER - C - COMPARE board and outside indications on Damper position and Air Preheater (634E0001), status
CCR - D - PLACE appropriate Damper in Manual in current position
1.2 Complete Supplemental Actions