634 Loss of Air Preheater (64-EOP-5025) Flashcards

1
Q

CCR - 1.1.1 - VISUALLY VERIFY the following Dampers indicate OPEN at Reactor Heater (634F0001), and on DCS:
- Natural Draft Door
- Stack Damper

A

CCR - 1.1.2 - If either Damper is closed,
CLOSE Reactor Heater Fuel Gas Controller (64PC5134) to trip the Fuel Gas SIS system until air flow is re-established to Reactor Heater.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

OPER/CCR - 1.1.3 - ENSURE the heater Fuel Gas SIS system automatically shuts down

A

OPER - 1.1.4 - CLOSE the Fuel Gas supply isolation valves to 64F0001, Reactor Feed Heater burners.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

CCR - 1.1.5 - ADJUST Stack Damper as needed for desired draft

A

1.2 - Complete Supplemental Actions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly