BK 100 Chpt 7-9 Flashcards

1
Q

What is the definition of “lobby” when referring to elevators and their use?

A

The floor of the elevator will respond to upon recall.It may be the main floor or any other level that best serves the needs of emergency personnel for firefighting or Rescue purposes. This floor will also contain the “emergency service switch”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where shall smoke detectors be placed?

A

Adjacent to the elevator at each landing. Usually on each floor except the lobby

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What happens during phase 1, recall phase?

A

Elevators will respond non-stop to the lobby and ignore all other call request

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Besides manually recalling elevators, how else may phase 1 be initiated?

A

Automatic elevators traveling more than 50 feet (or more than 25 feet, if new after 10/06/1975) may be recalled to the lobby by sensing devices (smoke detectors)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is phase 2?

A

Override phase, when utilized by firefighters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

All automatic elevators traveling over how many feet or more above the lowest grade level may be recalled to lobby by smoke detectors or manually?

A

70 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Utilizing the elevators for us sent in investigations or firefighting operations shall only be for reported locations above what floor?

A

The sixth floor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Elevators shall not be taken closer than how many floors to the reported fire floor or floor with alarm activation?

A

Two floors below the reported location or lowest floor with an alarm activation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If elevators automatically recall, must the elevator recall switch still be used?

A

Yes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What types of elevators shall not be used until determined safe by FD personnel on the desired floor and approved by IC to use?

A

Elevator is not equipped with phase 2 emergencies Firefighter service, freight elevators

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If the building is equipped with split banks elevators, do not use an elevator that services the fire floor if a lower Bank reaches within how many floors of the fire floor?

A

Five floors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What type of elevators should be avoided whenever possible?

A

Blind shaft elevators

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The presence of what in the elevator or shaft will dictate the elevator not be used?

A

Fire, smoke, water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Prior to going aloft in elevator, members must don what?

A

Facepiece

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What tool shall remain in the elevator car with the operator?

A

Dry chem extinguisher

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If an Engine company is first on scene alone, may they utilize elevators for their ascent?

A

No, requires minimum of 5 people (4 fire attack, 1 elevator operator)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the purpose of the bypass function on the elevator?

A

Once building has been determined safe, but still enough residual smoke to actuate the detector to prevent the elevators from operating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Elevators installed after October 1985 must have what feature for emergency personnel?

A

Call cancel Button

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What is the required fire flow for a class 1 dry standpipes?

A

500 GPM her riser

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What are the requirements which dictate where the outlets are located?

A

Every point in the structure must be reachable by a 30 foot stream from a nozzle with/100 feet of hose

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What are the flow requirements for wet standpipes at psi slowing 3 the roof outlet?

A

Pre-48 = 8 psi flowing 20 GPM
48-59 = 12 psi flowing 35 GPM
60-70 = 15 psi slowing 35 GPM
70- present= 30 psi flowing 35 GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What were building heights limited to and when did that restriction go away?

A

150 feet and 1960

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Why are the Jockey pumps installed?

A

To make a minor leakage rates in the system pressure and prevent the fire pump from continually starting and stopping

24
Q

What is the required fire flow for class three combinations standpipe?

A

1000 GPM per riser

25
Q

What is the required flow for each 2 1/2” outlet on a class III system?

A

300 GPM

26
Q

What years were looped systems be found?

A

1983 - 1988

27
Q

When are pressure regulating device is required?

A

Any standpipe outlet where static pressure exceeds 150 psi

28
Q

What are pressure regulating device is required to provide?

A

80–125 Psi Flowing 300 GPM

29
Q

What are fire pumps required to pump?

A

Pump 150% of rated capacity and not less than 65% of capacity for a minimum of 15 minutes

30
Q

What is the minimum flow rate for the vane type water flow switch?

A

4 to 10 GPM

31
Q

When should the water flow alarm sound?

A

Within 20 to 60 seconds of water flowing

32
Q

Where are pressure restricting devices found?

A

When static pressure is between 135 and 150 psi

33
Q

If you remove the restricting mechanism what must be done?

A

Leave a member at the outlet to control flow

34
Q

On site water supply must supply what GPM for the standpipe for buildings 1974 between 75’ and 150’?

A

Calculated sprinkler fire flow for the most demanding rectangular area of the building for 30 minutes, PLUS an additional 100gpm

35
Q

On site water supply must supply what GPM for the standpipe for buildings 1974 between 150’ and 275’?

A

500GPM for the first riser plus 250GPM for each additional riser, for 30 mins

36
Q

For buildings exceeding 275’, what size water tank may be found?

A

45,000 gallons to 105,000 gallons

37
Q

How many methods must there be to fill the tank?

A

2 methods

38
Q

What size pipe and what time requirement must the tank be filled in?

A

2” minimum diameter pipe to fill within 12 hrs or if after 1983, a pipe to refill within 8 hrs

39
Q

Buildings under construction of what height shall have a minimum of ONE standpipe for the construction phase?

A

6 or more stories

40
Q

Buildings under construction with temporary standpipes over 150’ shall have what?

A

Manually started fire pumps

41
Q

What is the fire pump required to pump during its test?

A

150% of rated capacity and a pressure not less than 65% of rated pressure for at least 15 minutes

42
Q

How can you distinguish between test valves and FDC valves?

A

FDCs always have female threads, Test valves have male threads

43
Q

What psi above the fire pumps psi should the jockey pump be set at?

A

5-10 psi above the fire pumps starting pressure

44
Q

Since 1974, buildings over 275’ have how many fire pumps?

A

Three, one electric, two diesel

45
Q

How much fuel should the diesel pumps have available?

A

Post ‘74 -8 hours, ‘60-‘74-4 hours

46
Q

What is the START and STOP pressure for fire pumps as related to system pressure? (Cut In/Cut Out)

A

STOP- 10 psi below system pressure

START- 50psi below System pressure

47
Q

What is the run out time set for?

A

7-10 minutes for electric pumps, 30 min for diesel

48
Q

Where should salvage operation begin?

A

Area where the greatest loss is expected

49
Q

A 2” line at 200gmp adds how many pounds to the structure?

A

1670 pounds per minute

50
Q

A 2 1/2” line at 325 adds how many pounds to the structure?

A

2800 pounds per minute

51
Q

Any switching of the air handling controls should be done cautiously and under direction of who?

A

The IC

52
Q

Rooms with an occupancy load of what will have public address communications?

A

50 or more

53
Q

The telephone number of the Fire control room should be given who?

A

MFC, IC, Fire attack, Lobby control

54
Q

What is the minimum size of the Fire control room?

A

200 sqft

55
Q

Emergency power shall operate within how long of the power failure?

A

10 seconds

56
Q

How many sound powered phones must they have?

A

7 (6 removable and one permanently attached)