1.1 IMMEDIATE ACTIONS

Oper 1.1.1 - DIVERT/SHUTDOWN feed to unit @ plot edge if emergency allows.

A

CCR/Oper 1.1.2 - CONTINUE sweeping the unit with Hydrogen if the emergency allows the compressors to run. IF not, SHUTDOWN the compressor servicing 631 unit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

CCR/Oper 1.1.3 ISOLATE 631 unit from 630 using 61FV0013, Hydrogen to Rx if, 630 unit can safely run. IF hot sweep is possible on 631 unit, MARK this step N/A and continue.

A

CCR 1.1.4 - ENGAGE the Hydrocarbon Feed bypass on the 61HS0009A DCS & 61HC5214 SIS, with the process hydrogen and hydrocarbon feed flows above their low trip points. (If emergency allows for a Hot Hydrogen Sweep. If not, omit this step and continue to next step.)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Oper 1.1.5 - REMOVE 631P0004A/B, Feed Pump from service.

A

CCR/Oper 1.1.6 - REMOVE 61FC0008, 631 Feed Flow Controller form service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

CCR/Oper 1.1.7 - REMOVE 61LV0026, Rx Effluent Flash Drum Bottoms Release regulator from service.

A

CCR/Oper 1.1.8 - REMOVE LV0099, Flash Drum Sour Water Release
NOTE: (Not In Service)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

CCR/Oper 1.1.9 - REMOVE 61LV0150, 631D0040 Flash Drum Sour Water Release.

A

Oper 1.1.10 - REMOVE 631P0015/B, Condensate Injection Pump from service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Oper 1.1.11 - BLOCK IN steam to the 1st and 2nd stage preheaters.

A

Oper 1.1.12 - REMOVE 631P0101A/B Stripper Bottoms pump from service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

CCR/Oper 1.1.13 - REMOVE 61FV0125/LV0025 Stripper Bottoms Level Controller from service.

A

Oper 1.1.14 - REMOVE the 631P0005, Stripper Overhead Pump from service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

CCR/Oper 1.1.15 - REMOVE 61LC0009 Stripper Overhead Receiver Level Controller from service.

A

CCR/Oper 1.1.16 - REMOVE Amine Injection from service.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Oper 1.1.17 - REMOVE 61P0030A/B, DSO Injection Pump from service.
NOTE: (Not In Service)

A

Oper 1.1.18 - IF in Renewable Diesel service, CLEAR 631 Renewable Diesel normal release line with 635 Diesel, by performing the following:

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

CCR A. NOTIFY Oil movements of intent to clear the 631 Renewable Diesel normal release line with 635 Diesel.

A

Oper B. LINE UP 635 Diesel to the 631 Normal release line.

Oper C. CLOSE the 631 product release valve to prevent 635 Diesel from backing into the unit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

1.2 SUPPLEMENTAL ACTIONS

CCR/Oper 1.2.1 - NOTIFY FLS of the time we started backflowing 635 Diesel for accounting purposes.

A

THIS IS THE END OF THE PROCEDURE