534 Loss of Cooling Water Flashcards
1.1 IMMEDIATE ACTIONS
CCR 1.1.1 - INFORM 637 Operator of the loss of cooling water to 534
CCR 1.1.2 - IF cooling water isn’t restored immediately, PLACE PC1016 Depentanizer Reboiler Heater Fuel Gas Controller in MANUAL mode and close the fuel gas regulator.
CCR/Oper 1.1.3 - VENT Depentanizer Tower to Low Line as needed to prevent lifting Relief valve to the 534D0025 Flare Drum
Oper 1.1.4 - Bypass unit by opening valve on feed bypass line to 632 Unit located at East Plot Edge.
Oper 1.1.5 - SHUT DOWN Depentanizer Feed Pump (534P0029/A).
CCR 1.1.6 - Place the following Controllers in MANUAL and CLOSE:
-Depentanizer Feed Flow Controller (54FC0035)
-Depentanizer Bottoms Flow Controller (54FC0045)
-Depentanizer Reboiler Heater Fuel Gas Controller (54PC1016)
-Depentanizer Overhead Flow Controller (54FC0052)
Oper 1.1.7 - WHEN level in Depentanizer Accumulator (534D0023), is less than 20%, as indicated by Level Transmitter (54LT0024)
SHUT DOWN Reflux Overhead Pumps (534P0027 and 534P0032)
1.2 SUPPLEMENTAL ACTIONS
Oper 1.2.1 - CLOSE upstream valve on the following Control Valves:
-Depentanizer Overhead Flow Controller (54FC0052)
-Depentanizer Bottoms Flow Controller (54FC0045)
-Depentanizer Reboiler Heater Fuel Gas Controller (54PC1016)
Oper 1.2.2 - Close block valves on Fuel Gas line located at each Depentanizer Reboiler Heater Burner.
THIS IS THE END OF THE PROCEDURE