The safe shutdown earthquake (SSE) and the operating basis earthquake (OBE) magnitude readings are
0.20g and 0.10g, respectively
The seismic monitoring system is located…
…only in Unit 1.
The purpose of the seismic monitoring system is…
… to detect and record seismic activity and determine its magnitude.
If any accelerometer exceeds its setpoint…
… it will cause all recorders to start.
The Seismic Monitoring Panel receives power from…
distribution panel NNN-D11.
When seismic motion is reported or the SEISMIC OCCURRENCE alarm is annunciated in the control room, the STA is required to perform…
… a Level 1 evaluation within 1 hour.
E-plan classifications must be made…
… within 15 minutes of when indications are available which show that an EAL has been met or exceeded.
Summarize actions to take if the ground motion is greater that OBE.
Primary action is to notify each Unit of need to shutdown to mode 3 for any Unit that is in mode 1 or 2, and ensure that alarm response procedures are carried out for system isolation and inspection.
- Perform emergency plan classification
- If an OBE has been exceeded, all three units must be shutdown to mode 3.
- Suspend fuel handling operations.
- Various plant inspections and walkdowns.
When ground motion is between ____ and OBE then…
For cases where an event has exceeded 0.01g but not the OBE, the Analysis of Seismic Event procedure requires communication to the Unit 1, 2 ,3 SM, component/system inspections, verification that AFN-P01 and associated