Class 4.16 kV Flashcards
Which of the following components IS NOT supplied by power from PBA-S03? A. 'A' Normal Chiller B. 'A' Auxiliary Feed Pump C. 'A' Essential Spray Pond Pump D. 'A' Essential Cooling Water Pump
B
Describe the ESF Service Transformers.
NBN-X03 and NBN-X04 receive 13.8 KV power from NAN-S03 and NAN-S04 and supply 4.16 KV power to PBA-S03 and PBB-S04
What are the three Load Centers supplied by Train A PBA-S03?
PGA-L31
PGA-L33
PGA-L35
The ‘A’ DG is running with its output breaker PBA-S03B closed, loaded to 5.2 MW. PBA-S03 normal supply breaker PBA-S03L is closed. The CO places PBA-S03 alternate supply breaker PBA-S03K synch switch PBA-SS-S03K to ON and then places the breaker switch PBA-HS-S03K to CLOSE. Alternate supply breaker PBA-S03K will:
A. close. The DG supply breaker will open when the switch is released.
B. close. The normal supply breaker will open when the switch is released.
C. not close, because the normal supply breaker is closed.
D. not close, because the DG supply breaker is closed.
D
What loads directly powered from PBA-S03 are SIAS load shed?
‘A’ Normal Chiller
‘N’ Aux Feed Pump
What is different about ‘B’ train components and why?
‘B’ Train components necessary for safe shut down of the pant have local/local+remote switches to remove control room circuitry in the event of a control room fire. This is done to prevent spurious operations due to the fire.
What are the purposes of an anti-pumping relay?
1) Anti-Pumping
2) Prevent closure attempt of the breaker of closing springs are not charged.
PBA-S03 is currently being powered from DGA and the CO is going to parallel across the breaker to NBN-X03. After the sync selector switch is enabled, which voltages are indicated by “running” and “oncoming?”
“Running” is the PBA-S03 voltage, “Oncoming” is the voltage at the output of NBN-X03. This often leads to confusion when performing this operation. Remember that PBA-S03 and PBB-S04 are always considered “Running” and never “oncoming.”
PBA-S03 is being powered from the ‘A’ Diesel. The control room instructs the AO to close the PBA-S03 feeder breaker from NBN-X03. What will happen when the AO takes the CS-1 switch on the breaker cubicle to “shut?”
The breaker will not close as interlocks prevent paralleling power supplies locally.
List the ESF transformer trips.
1) Sudden pressure
2) Phase and ground overcurrent
3) Transformer differential
What indication do PBA and PBB under voltage relays provide in the Control Room?
Under their respective busses there are 8 white lights representing status of the relay. If the relay is actuated the light will be out. All 8 lights should normally be lit.
The CR has approved a clearance to remove the PT fuses for PBA-S03 during an outage. What will happen as soon as the fuse drawer is removed?
All 8 UV relays will detect an under voltage condition.
How is a LOP detected, and what coincidence is required for actuation?
Instantaneous undervoltage at 75% rated voltage, Time delay undervoltage at 90% for 30 seconds. 2/4 signals required for BOP ESFAS actuation.
What supplies control power for PBA-S03(PBB-S04)?
PKA-D21(PKB-D22)
Upon a SIAS signal, what is NOT load shed from PBA-S03 and PBB-S04?
A) AFN-PO1
B) Class Load Centers
C) NHN-M19, M20, M71, and M72
B.
Upon a SIAS load shed, what does not sequence back onto PBA-S03?
AFN-P01 and WCN-E01A
What are the protective features of the ESF transformers?
Sudden Pressure Relay
Transformer Differential
Phase and Ground Over-current
Explain degraded voltage vs. under-voltage with regards to 4.16kV Class buses. What coincidence will cause a LOP signal for the bus?
Degraded voltage: Below 90% rated voltage for ~30 seconds.
Under-voltage: Voltage drops below 75%.
2 out of 4 (for either condition) will initiate a LOP signal.
How does the operation of the Unit 1 class load center feeder breakers differ from those in the other two Units?
Due to initial plant design in Unit 1 where a SIAS load shed opened the LC feeder breaker and then sequenced it back on, an issue resulted in the breaker where the springs would not be sufficiently charged. Therefore, a jumper was installed to ensure the closing springs were charged under all conditions (vice just charging when the breaker opens).
Given the following Class (PG) Load Centers, list all the Class (PH) MCCs powered from each:
PGB-L36
PGB-L34
PGB-L32
PHB-M36 powered from PGB-L36
PHB-M34 powered from PGB-L34
PHB-M32 powered from PGB-L32
PHB-M38 powered from PGB-L32
Which MCC’s are SIAS Load Shed?
NHN-M19 and NHN-M71 (Load Group A)
NHN-M20 and NHN-M72 (Load Group B)
(ANNUNCIATOR) XFMR HI TEMP BUS UNDV 125VDC FAILURE
Alarm is generated by:
A high temp condition in the x-fmr
Bus UV -or-
Control Power Failure
Note: Alarm is only associated with PGA-L33
What are the three Load Centers supplied by PBB-S04?
PGB-L32
PGB-L34
PGB-L36
Name the Train A MCC’s.
PHA-M31
PHA-M33
PHA-M35
PHA-M37
Name the Train B MCC’s.
PHB-M32
PHB-M34
PHB-M36
PHB-M38
Which of the following components IS NOT supplied by power from PBB-S04? A. 'B' Normal Chiller B. 'B' Auxiliary Feed Pump C. 'B' Essential Spray Pond Pump D. 'B' Essential Cooling Water Pump
A
Describe the cooling system of the ESF transformers.
The ESF transformers are FA/OA (Forced Air/Oil Air) meaning air is blown across cooling fins filled with oil, causing natural circulation of the oil. The four fans turn on at a winding hot spot temperature of 70 C, when in AUTO.