AOP Flashcards
Unit 1 is at 100% power with all systems in a normal lineup.
LT HDR SYS TRBL alarm has come in.
Letdown flow is 0 gpm.
Letdown backpressure is 600 psig and oscillating.
Which of the following actions should the RO perform?
A. Close Letdown Isolation Valve CHB-UV-515
B. Throttle open the in-service letdown backpressure control valve CHN-PV-201P
C. Throttle open the in-service letdown control valve CHN-LV-110P
D. Bypass the letdown ion exchangers with CHN-HS-520
A
Unit 2 is at 100% power with all systems in a normal lineup.
ESF service transformer NBN-X03 faults.
With no further operator action, what will be the condition of the following valves?
1) Letdown isolation valve CHB-UV-515
2) Letdown isolation valve CHA-UV-516
3) Letdown isolation valve CHB-UV-523
A. OPEN, OPEN, CLOSED
B. OPEN, CLOSED, OPEN
C. CLOSED, OPEN, OPEN
D. CLOSED, OPEN, CLOSED
C
Unit 2 is at 100% power with all systems in a normal lineup.
Nuclear cooling water pump NCN-P01A trips on overcurrent.
Nuclear cooling water pump NCN-P01B does not automatically start.
With no further operator action, what will be the condition of the following valves?
1) Letdown isolation valve CHB-UV-515
2) Letdown isolation valve CHA-UV-516
3) Letdown isolation valve CHB-UV-523
A. OPEN, OPEN, CLOSED
B. OPEN, CLOSED, OPEN
C. CLOSED, OPEN, OPEN
D. CLOSED, OPEN, CLOSED
A
Unit 3 is at 100% power with all systems in a normal lineup.
Nuclear cooling water pump NCN-P01A trips on overcurrent.
Nuclear cooling water pump NCN-P01B has a sheared shaft.
The CO cross-connects EW ‘A’ train to supply NC priority loads.
The RO has performed 40AO-9ZZ05, Loss of Letdown, Appendix C, Extended Operations Without Letdown, and has secured all charging pumps.
What is the expected pressurizer level trend?
A. Pressurizer level will rise by 10% in 55 minutes
B. Pressurizer level will lower by 10% in 55 minutes
C. Pressurizer level will rise by 5% in 55 minutes
D. Pressurizer level will lower by 5% in 55 minutes
B
Unit 3 is at 100% power with all systems in a normal lineup.
Nuclear cooling water pump NCN-P01A trips on overcurrent.
Nuclear cooling water pump NCN-P01B has a sheared shaft.
The CO cross-connects EW ‘A’ train to supply NC priority loads.
The RO has performed 40AO-9ZZ05, Loss of Letdown, Appendix C, Extended Operations Without Letdown, and has secured all charging pumps.
Which of the following events would automatically isolate cooling water to the RCPs?
A. Containment pressure of 5 psig
B. EW ‘A’ surge tank high level alarm
C. Pressurizer pressure of 2400 psia
D. Fault on normal service transformer NBN-X01
A
Unit 1 is at 100% power.
Charging Pump Selector Switch CHN-HS-4 is in 1-2-3.
CHE-P01, ‘E’ Charging Pump, is isolated for pulsation dampener adjustment.
All other systems are in a normal lineup.
CHA-P01, ‘A’ Charging Pump, trips on a ground fault.
CHB-P01, ‘B’ Charging Pump, continues to run.
CHB-UV-515 automatically closes on high regenerative heat exchanger outlet temperature.
Pressurizer level is 50% and trending down.
Pressurizer pressure is 2240 psia and trending down.
Which of the following actions should be taken first?
A. Perform 40AO-9ZZ12, Degraded Electrical Power, and restore PBA-S03.
B. Perform 40AO-9ZZ05, Loss of Letdown, and restore letdown.
C. Perform 40AO-9ZZ02, Excessive RCS Leakage, and commence a 4-hour plant shutdown.
D. Trip the reactor and enter 40EP-9EO01, Standard Post Trip Actions
D
Unit 3 is at 100% power with all systems in a normal lineup.
All four channels of RU-142, Main Steam Line N-16 monitor, go into HIGH ALARM.
The CRS enters 40AO-9ZZ02, Excessive RCS Leakage.
Letdown flow lowers to 77 gpm and stabilizes.
Which of the following actions will be performed to mitigate the consequences of this event?
A. Immediately trip the reactor and enter 40EP-9EO01, Standard Post Trip Actions
B. Immediately start the standby charging pump.
C. Close ASN-V014 and ASN-V015 to isolate the unit from the auxiliary steam cross-tie header.
D. Place Steam Bypass Control System in EMERGENCY OFF.
C
Unit 2 is at 60% power with all systems in a normal lineup.
‘A’ and ‘B’ Charging Pumps are running with Charging Pump Mode Selector CHN-HS-4 in 1-2-3.
Pressurizer level is 41% and lowering.
PZR TRBL, Tave-Tref HI-LO, and AUTOMATIC MOTION INHIBIT are in alarm.
Which of the following AOPs should be entered?
A. 40AO-9ZZ02, Excessive RCS Leakage
B. 40AO-9ZZ05, Loss of Letdown
C. 40AO-9ZZ11, CEA Malfunctions
D. 40AO-9ZZ16, RRS Malfunctions
D
Unit 1 is at 100% power with all systems in a normal lineup.
A leak develops downstream of CHA-HV-524, Charging Header Isolation Valve.
40AO-9ZZ02, Excessive RCS Leakage, is entered, and Appendix E is performed to align the alternate discharge for all three Charging Pumps.
Which of the following charging system functions will be made available through this lineup?
A. Seal injection
B. RCS dilution
C. Auxiliary Spray
D. RHX cooling for letdown
B
Unit 1 is at 100% power with ‘B’ LPSI pump tagged out for planned maintenance.
All other systems are in a normal lineup.
A leak develops downstream of CHA-HV-524, Charging Header Isolation Valve.
40AO-9ZZ02, Excessive RCS Leakage, is entered, and Appendix E is performed to align the alternate discharge for the ‘A’ Charging Pump.
Which injection lineup should be used for charging into the RCS?
A. SIE-V508, cold leg injection, with ‘A’ HPSI piping, using loop 1 injection valves.
B. SIE-V508, cold leg injection, with ‘A’ HPSI piping, using loop 2 injection valves.
C. SIE-V509, hot leg injection with ‘A’ HPSI piping.
D. SIE-V509, hot leg injection with ‘B’ HPSI piping.
B
Unit 2 is at 100% power with all systems in a normal lineup.
Regulating group 5 CEAs are at 135” withdrawn. All others are fully withdrawn.
RCN-TT-111X, Loop 1A temperature, fails low.
Which of the following will occur within the next fifteen seconds?
A. CEAs will step inward
B. CEAs will step outward
C. Letdown flow will rise
D. Letdown flow will lower
C
Unit 1 is at 100% power with all systems in a normal lineup.
‘B’ CSAS inadvertently actuates due to multiple fuse failures.
Which of the following describes an operational impact of this failure?
A. Cooling water flow will be isolated to the normal chillers
B. Instrument air will be isolated to containment
C. Letdown will isolate
D. RCP control bleedoff will be isolated from the VCT
D
Unit 3 is at 100% power with all systems in a normal lineup.
‘A’ CSAS inadvertently actuates due to multiple fuse failures.
With no operator action, which of the following describes an operational impact of this failure?
A. Cooling water flow will be isolated to the normal chillers
B. Instrument air loads in containment will be supplied by backup nitrogen
C. SG blowdown will isolate
D. Letdown flow will rise
C
IAN-PV-52, Nitrogen backup to Instrument Air, will automatically open at a low pressure of: A. 75 psig B. 85 psig C. 95 psig D. 105 psig
B
Unit 2 is at 100% power with all systems in a normal lineup.
A pipe break downstream of the instrument air dryers causes a rapid drop in IA pressure
The CRS directs a reactor trip.
Which of the following valves will fail closed as IA system pressure drops?
A. Condensate pump mini-flow valves
B. Main feed pump mini-flow valves
C. Steam Bypass Control Valves
D. Atmospheric Dump Valves
C
Unit 1 is at 100% power with all systems in a normal lineup.
The solenoid burns out on IAA-UV-2, IA isolation to containment.
The RO notes CHA-UV-506, Seal Bleedoff containment isolation valve, has gone closed.
With no further operator action, letdown flow will ___(1)___, and seal injection flow will ___(2)___.
A. (1) rise; (2) rise
B. (1) rise; (2) lower
C. (1) lower; (2) rise
D. (1) lower; (2) lower
C
Unit 3 is at 100% power with all systems in normal lineup.
The solenoid burns out on IAA-UV-2, IA isolation to containment. IAA-UV-2 fails closed.
Which of the following mitigating strategies should be performed first?
A. Cross tie service air to the containment instrument air header
B. Cross tie the containment low pressure nitrogen header to the containment instrument air header.
C. Trip the reactor, trip the RCPs, and isolate controlled bleedoff using CHA-UV-506, CHB-UV-505, and CHA-HV-507.
D. Perform 40AO-9ZZ05 and restore letdown
A
Unit 3 is at 4% reactor power, currently performing power ascension.
‘A’ MFP is feeding steam generators in automatic.
A ‘B’ train MSIS actuates due to multiple fuse failures.
In accordance with 40AO-9ZZ17, Inadvertant PPS-ESFAS Actuations, which pumps may be used to feed steam generators?
A. Main feed pumps or Auxiliary Feed Pumps
B. AFN, AFA, or AFB feed pumps ONLY
C. AFA or AFB feed pumps ONLY
D. AFN or AFB feed pumps ONLY
C
Unit 2 is at 100% power with all systems in a normal lineup.
An inadvertent ‘A’ train actuation of which of the following systems will require entry into LCO 3.0.3?
A. CIAS
B. MSIS
C. CSAS
D. RAS
A
Unit 1 is at 100% power with all systems in a normal lineup.
All CEAs are at the Upper Electrical Limit.
CPC/CEAC trouble alarm is received.
CEAC shows CEA #8, a shutdown group A CEA, is now at 145 inches withdrawn.
The reactor has not tripped. What action is required?
A. CPCs should have tripped the reactor. Immediately perform a manual reactor trip.
B. Enter 40AO-9ZZ11, CEA Malfunctions, and commence a 20% power reduction.
C. AOP/EOP entry is not required. Enter LCO 3.1.6 condition A and withdraw the CEA to within limits in two hours.
D. AOP/EOP entry is not required. LCO 3.1.6 is currently met.
C
Unit 1 is at 100% power with all systems in a normal lineup.
A slipped CEA causes the following indications:
Pressurizer level is trending down.
Reactor Power lowers to 99% and stabilizes.
‘A’ CPC has tripped on Hi LPD and Lo DNBR. The other CPCs have not tripped.
Which of the following events would cause these indications?
A. A Regulating Group 5 CEA has slipped to 120” withdrawn.
B. A Regulating Group 4 CEA has slipped to 120” withdrawn.
C. A Regulating Group 1 CEA has slipped to 120” withdrawn.
D. A Shutdown Group B CEA has slipped to 120” withdrawn.
B
Unit 3 is at 100% power with all systems in a normal lineup.
A RRS failure causes continuous inward CEA motion.
After entering 40AO-9ZZ17, RRS Malfunctions, CEDMCS is placed in STANDBY.
CEA motion stops with Regulating Group 5 at 90”.
Tcold stabilizes at 555 degrees.
Reactor power stabilizes at 96%.
Subsequently, CEA 87, a Regulating Group 4 CEA, slips to 138” withdrawn.
What is the required action?
A. Trip the reactor and perform SPTAs.
B. Enter 40AO-9ZZ11, CEA Malfunctions, and commence a power reduction of at least 20%.
C. Enter 40AO-9ZZ11, CEA Malfunctions, and withdraw CEA 87 to the height of the other CEAs in its group when the problem has been identified. Power reduction not required.
D. Withdraw CEA 87 to the height of the other CEAs in its group when the problem has been identified. AOP entry is not required.
A
Unit 2 is at 100% power with all systems in a normal lineup.
A RRS failure causes continuous inward CEA motion.
After entering 40AO-9ZZ17, RRS Malfunctions, CEDMCS is placed in STANDBY.
CEA motion stops with Regulating Group 5 at 55”.
Tcold stabilizes at 553 degrees.
Reactor power stabilizes at 94%.
Subsequently, the CO notices CEA 87, a Regulating Group 4 CEA,is at 143” withdrawn.
What is the required action?
A. Trip the reactor and perform SPTAs.
B. Enter 40AO-9ZZ11, CEA Malfunctions, and commence a power reduction of at least 20%.
C. Enter 40AO-9ZZ11, CEA Malfunctions, and adjust CEA 87 to the height of the other CEAs in its group when the problem has been identified. Power reduction not required.
D. Adjust CEA 87 to the height of the other CEAs in its group when the problem has been identified. AOP entry is not required.
D
Unit 1 was at 100% power with all systems in a normal lineup.
CEA 14, a Regulating Group 5 CEA, slips to 120” at 1200.
The CRS entered 40AO-9ZZ11, CEA Malfunctions.
The plant has been downpowered to 80% power.
Troubleshooting has determined that CEA 14 cannot be moved by CEDMCS.
What action is required?
A. The unit may not remain at power indefinitely. The unit must be in MODE 3 by 1600.
B. The unit may not remain at power indefinitely. The unit must be in MODE 3 by 1800.
C. The unit may not remain at power indefinitely. The unit must be in MODE 3 by 2000.
D. Align the remaining Regulating Group 5 CEAs with CEA 14. In this condition, compliance with all LCOs can be established.
D