Non Class Electrical Flashcards
What are the loads on NBN-S01?
Turbine Cooling Pump A Plant Cooling Water Pump A Nuclear Cooling Water Pump A Heater Drain Pump B Normal Chiller B Condensate Pump A Condensate Pump B
State the possible characters for the second position in the electrical distribution system nomenclature. example: PBA-S03
A - 13.8 KV B - 4.16 KV G - 480 VAC LC H - 480 VAC MCC K - 125 VDC N - 120 VAC INST E - 4.16 KV DG Q - 120 VAC UPS
State the possible characters for the third position in the electrical distribution system nomenclature. example: PBA-S03
A - Train A B - Train B C - Train C D - Train D N - Non Train
State the possible characters for the fourth position in the electrical distribution system nomenclature. example: PBA-S03
D - Distribution Panel
M - Motor Control Center (Bus - generally < 50 HP loads)
L - Load Center (generally > 50 HP loads)
S - Switchgear
State the possible characters for the last two positions in the electrical distribution system nomenclature. example: PBA-S03
The last two numbers are particular to the equipment.
What is the Normal and Alternate Control Power Supply to NAN-S06?
NKN-M46 (Norm)
NKN-M45 (Alt)
On 13.8kV and 4160V Switchgear, the RED light indicates ….
Breaker CLOSED
Continuity through breaker Trip Coil
NOTE: If the RED light is NOT lit, the trip ckt may NOT function
On 13.8kV and 4160V Switchgear, the Bright GREEN light indicates ….
Breaker TRIPPED on fault or breaker racked to the TEST position.
A 480 VAC Load Center breaker has just been CLOSED, what is the status of the closing spring?
Discharged
After the bkr has been CLOSED, the closing spring remains discharged
When does the tripping spring charge for 13.8 kV and 4160V bkrs?
As the bkr closes, the tripping spring is charged.
Once the bkr contacts reach the full CLOSED position, the bkr latches in this position with the tripping spring fully charged and ready to OPEN the contacts.
What two functions does the 13.8kV and 4160V anti-pumping relay provide?
- Ensures that the bkr only attempts to close ONCE per control switch operation
- Prevents a bkr closure attempt with an uncharged spring
On U1 Control Panel B01, what do the two digital meters located on the vertical section of the control board indicate?
East and West bus voltages in the SRP Switchyard
List the transmission lines connected to the “ring bus”?
Westwing #1 Westwing #2 Rudd Hassayampa #1 Hassayampa #2 Hassayampa #3 Colorado River
What is the electrical capacity of one Startup Transformer (i.e. NAN-X01, X02 or X03)?
1/2 the non-Class 1E loads of one Unit and 2 trains of ESF loads, one of which is from another Unit, during Unit trips or during startup/shutdown operation.
Startup Transformer temperature is < 70C, what is the cooling mode?
Cooling is accomplished by natural circulation of the oil. Fans are NOT operating.
One pump and a bank of fans have just started on a Startup Transformer (i.e. NAN-X01, X02 or X03), what is the temperature of the transformer?
70C
At 70C, a thermal control device automatically turns on one oil pump and bank of fans
Temperature on the Startup Transformer is >75C, what is the cooling mode?
A second oil pump and bank of fans are energized, and operate in conjunction with the first pump and bank of fans to cool the Startup Transformer.
List the 4 Startup Transformer protective relays that detect a fault and isolate the transformer.
Differential Current
Neutral Ground Fault
Overcurrent
Sudden Pressure
The intermediate buses (NAN-S05 and S06) associated with Unit 1 supply the …
Water Reclamation Facility (WRF)
Startup Switchyard 480V LCs (NGN-L43 & L44)
525kV Switchyard - NAN-S05 powers SRP Swyd & Batt Chgrs
NAN-S03 & S04 receive control power from …
NKN-D41 (Non-Class 125 VDC) and NKN-D42 (Non-Class 125VDC) respectively
In order for an automatic FAST BUS Transfer to occur on NAN-S01 and NAN-S02, what conditions must be satisfied?
The BUS XFR SWITCH must be in AUTO
Generator trip must have occurred or UAT trip
Early ‘b’ contact on NAN-S01 norm supply bkr closed
Sync Check relay must be satisfied
NO bus lockout
Voltage must be available on NAN-S03 and NAN-S04