Control Building HVAC Flashcards

1
Q

Unit 2 is at 100% power with all systems in a normal lineup.
Control Room Normal AHU HJN-A02 trips on thermal overload.
Which of the following rooms no longer have cooling?
A. 160’ Cable Spreading Room
B. 120’ Communication Equipment Room
C. 100’ Train A ESF Switchgear Room
D. 74’ Control Building Basement

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Unit 1 was at 100% power with all systems in a normal lineup.
A LOCA results in a reactor trip, a SIAS, and a CIAS.
All equipment operates as designed.
The 120’ Control Building Communications Equipment and Inverter Rooms are being cooled by:
A. nothing
B. ‘B’ Train Control Room Essential AHU HJB-F04
C. Control Room Normal AHU HJN-A02
D. Control Building Normal AHU HJN-A05

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Which of the following areas is NOT supplied by Control Building Normal AHU HJN-A01?
A. 74’ Control Building Basement
B. 120’ Cable Spreading Room
C. 120’ Communications Equipment and Inverter Rooms
D. 160’ Cable Spreading Room

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

HJA-HS-58 controls the following:
Control Building Normal AHU Essential Return Duct Isolation Damper HJA-M36
Control Building Normal AHU Essential Return Duct Isolation Damper HJA-M51
ESF Normal AHU Essential Supply Duct Isolation Damper HJA-M66
ESF ‘A’ Essential AHU Essential Supply Duct Isolation Damper HJA-M62
All dampers were in their normal position when SIAS actuated.
All dampers are now closed.
What is the indication on HJA-HS-58?
A. Dark
B. Red light ONLY
C. Green light ONLY
D. BOTH Red and Green lights

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Unit 1 is at 100% with all systems in their normal lineup.
‘A’ Battery Room Normal Exhaust Fan HJN-J01A is running.
HJA-HS-81, the operating switch for ‘A’ Battery Room Essential Exhaust Fan HJA-J01A, is placed to START and then released.
Which of the following is true concerning the equipment response?
A. HJA-J01A will not start because HJN-J01A is running.
B. HJA-J01A will start. HJN-J01A will continue to run.
C. HJA-J01A will start. HJN-J01A is interlocked to immediately trip when HJA-J01A is running.
D. HJA-J01A will start. HJN-J01A will trip on high duct differential pressure.

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which of the following components can NOT be controlled from the Remote Shutdown Panel?
A. ‘B’ CR Essential AHU HJB-F04 OSA intake damper HJB-M02
B. ‘B’ CR Essential AHU HJB-F04 OSA intake damper HJB-M03
C. ‘B’ Battery Room Essential Exhaust Fan HJB-J01B
D. ‘B’ CR Normal AHU Isolation Dampers HJB-M01/M55

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Unit 3 is at 100% with all systems in their normal lineup.
RU-29 fails high, resulting in an actuation of both trains of CREFAS.
All equipment operates as designed.
Control Building Normal AHU HJN-A01 is ___(1)___, and Control Room Normal AHU HJN-A02 is ___(2)___.
A. (1) running; (2) running
B. (1) running; (2) not running
C. (1) not running; (2) running
D. (1) not running; (2) not running

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Refer to drawing 01-E-HJB-0024.
Unit 1 is at 100% power with all systems in their normal lineup.
An ammonia spill in the North Yard causes the control room to manually initiate both trains of CRVIAS.
Subsequently, RU-30 fails high, resulting in an actuation of both trains of CREFAS.
All equipment operates as designed.
The RO places handswitch HJA-HS-36 for CR Essential AHU Outside Air Intake Damper HJA-M02 to the OPEN position.
The OVERRIDE light on HJA-HS-36 will be ___(1)___ and the damper will be ___(2)___.
A. (1) on; (2) closed
B. (1) on; (2) open
C. (1) off; (2) closed
D. (1) off; (2) open

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The ‘A’ CR Normal AHU discharge isolation damper (HJA-M01) is OPEN and the ‘B’ discharge isolation damper (HJB-M01) is CLOSED. The RO goes to start the CR Normal AHU (HJN-A02); will the AHU start?

A

Interlocks exists that will prevent the CR Normal AHU (HJN-A02) from starting unless both of its discharge dampers (HJA-M01 & HJB-M02) are OPEN. In addition, a closure of either of these dampers will trip off the AHU.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Why are the CR Normal AHU isolation (suction and discharge) dampers powered from their respective PK buses?

A

The “B” essential air filtration unit (HJB-F04) utilizes the same duct work as the Normal AHU (HJN-A02), the dampers are necessary to isolate the Normal AHU from the essential ventilation system when required (i.e. SIAS, LOP, CREFAS, CRVIAS).

The isolation dampers are air operated and fail close on a loss of air or power.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The Control Building Normal AHU (HJN-A01) is interlocked with suction damper (HJA-M51) such that …

A

if the damper is CLOSED the AHU will NOT start and if the damper closes while the AHU is running, the AHU will stop.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

If the ESF Switchgear Normal AHU (HJN-A03)discharge damper (HJA-M66) is OPEN and discharge damper (HJB-M66) is CLOSED, will the AHU start if given a start signal?

A

Yes, the ESF Switchgear Normal AHU (HJN-A03) will run if only one of its discharge dampers HJA-M66 or HJB-M66 is OPEN.

Conversely, the AHU will stop when both dampers go CLOSED.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The CR Essential AHUs (HJA-F04 & HJB-F04) will start on which ESFAS and BOP-ESFAS signals?

A
SIAS
CSAS
CREFAS
CRVIAS
LOP
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A SIAS has initiated and the intake dampers (HJA-M02/M03 and HJB-M02/M03) to the CR Essential AHUs ‘A’ and ‘B’ have gone OPEN. The Control Room has determined to err on the conservative side and recirculate the air to the CR. What method or methods can the RO use to shut the intake dampers?

A

The RO can override the SIAS to shut the intake dampers or manually initiate a CRVIAS.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The ESF Equipment Room Essential AHUs (HJA-Z04 & HJB-Z04) are interlocked with their respective discharge dampers (HJA-M62 or HJB-M58) in that if the damper …

A

goes CLOSED the fan will trip.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The Battery Room Normal (HJN-A01A, B, C, D) will automatically STOP if its …

A

respective room CO2 flood system actuates -OR-
its associated Essential Exhaust fan starts either from being manually started from the CR -OR-
from a SIAS or LOP, (sensed by a high D/P across the Essential Fan)

17
Q

What is the status of the thermal overload protection for the Battery Room Essential Exhaust fans (HJA-J01A,B and HJB-J01A,B) during a SIAS?

A

The thermal overload protection is BYPASSED.

18
Q
(ANNUNCIATOR)
CONT BLDG
HVAC
SYS
TRBL
A
The HJ HVAC system is so large, there are quite a few inputs to this alarm window.  These include problems with the:
Normal Control Building AHU
Control Room AHU
ESF Equipment Room Essential AHUs
ESF Equipment Room Normal AHUs
Battery Room Exhaust fans

Note: In most cases, an AO would need to be dispatched to investigate.

19
Q
(SESS Component Alarm)
CR ESS
AHU
FAN A
F04
A

WHITE section (SEIS) comes in when:

  • LC bkr is NOT in the OPERATE position
  • Control Power fuse is blown
  • Fan has tripped due to an electrical fault

BLUE section (SEAS) comes in when:

  • The bkr is OPEN when it’s actuated position is CLOSED
  • OPEN control power supply bkr
  • Blown control power fuses for the fan
  • Fan or motor is binding
20
Q
(SESS Component Alarm)
ESF
RMS ESS
AHU A
Z03
A

WHITE section (SEIS) comes in when:

  • MCC bkr is OPEN
  • Control Power fuse is blown
  • Motor O/Ls are OPEN

BLUE section (SEAS) comes in when:

  • OPEN supply bkr when it’s actuated position is CLOSED (Fan running)
  • Blown Control power for the motor
21
Q
(SESS Component Alarm)
ESF
RMS ESS
AHU A
Z04
A

WHITE section (SEIS) comes in when:

  • MCC bkr is OPEN
  • Control Power fuse is blown
  • Motor O/Ls are OPEN

BLUE section (SEAS) comes in when:

  • OPEN supply bkr (Fan not running) when it’s actuated position is CLOSED (Fan running)
  • Blown Control power for the motor
  • Damper HJA-M62 is fully CLOSED.
22
Q
(SESS Component Alarm)
BAT RM A
ESS EXH
FAN
J01A
A

WHITE section (SEIS) comes in when:

  • MCC bkr is OPEN for either fan
  • Control power fuse is blown for alarming fan
  • Motor O/Ls are OPEN for either fan
BLUE section (SEAS) comes in when:
- MCC contactor is OPEN (Fan not running) when its actuated position is CLOSED (Fan Running)
23
Q

Unit 1 is at 100% power with all systems in a normal lineup.
The CO initiates ‘A’ CREFAS and ‘A’ CRVIAS from B05.
All components actuate as designed.
Ten minutes later, PKA-M41 develops a ground and de-energizes.
What is the position of Control Room Essential AHU HJA-F04 outside air intake damper HJA-M03?
A. Held open by air pressure
B. Held closed by air pressure
C. Open due to relief of air pressure
D. Closed due to relief of air pressure

A

C