MSA G1 SCBA Flashcards
What are the 10 main components of your SCBA?
- Face piece
- HUD
- Regulator w Bypass
- Speaker Module
- Harness and Carrier Assembly
- Cylinder w Gauge and Valve
- Pressure Reducer w UAC and Low Air Warning Bell
- Power Module
- Control Module w TIC
- Quick Fill Pouch
What is the purpose of Function A Test?
To see that the face piece and regulator can hold negative pressure.
What is the purpose of Function B test?
To check the speaker and regulator function.
What is the purpose of Function C Test?
To check Control Module, Power Module, HUD, and Primary Low Pressure Warning Device.
What are the 3 Pre-Entry Checks?
Tug Test, By-Pass, Negative Pressure
What is the minimum pressure your cylinder should have at the beginning of your shift?
4000 PSI
What pressure range is 4 green lights on the HUD?
75-100%
What pressure range is 3 green lights on the HUD?
50-74%
What pressure range is 2 yellow flashing lights on the HUD?
36-49%
What pressure range is 1 Red Flashing light on the HUD?
0-35%
At what pressure does the low warning bell engage?
1575 psi
At what pressure does the low pressure warning bell cease operation?
200 psi
The pressure reducer brings air psi to…
102-113 psi
What is the litre volume of a 45 minute psi cylinder?
1870 litres
What is the percentage of oxygen in normal air? IFSTA p203
19.5% but can range to 21%
19.5 would be the minimum.
Above 23 would be oxygen rich.