Ch11 Mechanical Ventilation/Tactical Ventilation Flashcards
Tactical ventilation is the planned and systematic removal of heated air, smoke, gases or other airborne contaminants from a structure, replacing them with cooler and/or fresher air to meet the incident priorities… p493
Correctly implemented, tactical Ventilation helps to achieve incident priorities of “Life Safety, Incident Stabilization, and Property Conservation.” (LIP)
What is Positive Pressure Attack? p509-510
PPA is used in the initial stages of an incident to make the structure safe for fire attack.
This is when a fan is set up at a door way to increase the pressure inside the structure relative to the atmospheric pressure outside the structure.
This pressure differential carries toxic smoke, gases, and heat from the entrance where fans were placed to an exhaust opening located as close to the fire as possible.
The two main considerations for PPA are fire location and exhaust to intake ratio (CFD wants .75 to 1.75 greater exhaust size to intake size ratio).
The ratio compares the surface area of all exhaust openings with the surface area of all intake openings.
What is Positive Pressure Ventilation? p511-512
This is when a fan is setup at a door way of a structure and is used to positive pressurize the structure to assist in overhaul to remove smoke and gases after fire suppression. This accelerates natural ventilation.
Positive Pressure Pressurization…
This uses one or more high-output fans to over pressurize an enclosed compartment and preventing additional smoke, gases, and heat from entering an area.
PPP could be used to:
Prevent fire extension into adjacent occupancies in a strip mall
Confine a garage fire and pressurize the adjoining house
Confine an attic fire and pressurize rooms below
Prevent fire extension into adjacent townhouses
PPP would not be an appropriate tactic when:
The fire location has not been established
The fire is known to be spreading beyond origin
There are natural gas leaks
What is a flow path?
The volume between an inlet and an outlet that allows the movement of heat and smoke from the higher pressure within the fire area towards the lower pressure areas accessible via doors and windows within a structure.
When setting up an exhaust opening for mechanical ventilation, approximately what size should it be?
The exhaust opening should be 3/4 to 1 3/4 the size of the entrance to where the fan is placed. Bigger is better.
At what angle should fans be placed at a door way before being started?
90 degrees to door way. Once the IC has given the order, place in front of doorway so sufficient air cone coverage of doorway.
What fan positioning option has the most output?
Single (basic)
Series (one fan is placed behind another)
Parallel (two fans are placed side by side)
V-Point (two fans positioned parallel and point in a V configuration towards the door)
Answer: V-Point. This option provides the highest volume of air.
Single (basic)
Series (one fan is placed behind another, 30% more than single)
Parallel (two fans are placed side by side, 30% more air)
V-Point (two fans positioned parallel and point in a V configuration towards the door. This combination has 10% more air flow than SERIES or PARALLEL)
Tactical ventilation is the planned and systematic removal of heater air, smoke, gases or other airborne contaminants from a structure, replacing them with cooler and/or fresher air… p493
Correctly implemented, tactical ventilation helps achieve incident priorities of life safety, incident stabilization, and property conservation. However, if ventilation is incorrectly applied, the results can traumatize occupants, firefighters, and the structure.
Being in control of the fire means using ventilation and water application to control its behaviour. In terms of ventilation, firefighters control the flow of oxygen, smoke, and hot gases to then control the rate of fire growth and spread… p494
ventilation also allows firefighters to control where hot gases and smoke exhaust from a structure. Controlling exhaust openings may improve visibility inside the structure so that interior crews can work more effectively. Exhaust openings can also be used during overhaul to facilitate the removal of smoke or toxic gases after fire extinguishment.
To control the flow path, firefighters can be positioned at doors that the crew passes through along their entry path… p494
Normally, this is just the entry door in residential fires. Their role would be to close any doors as much as hoselines will allow.
An effective way of controlling ventilation is to cover openings rather that creating more openings. Before interior attack, closing exterior doors and windows or using smoke control devices and/or wind control devices to cover ventilated windows will reduce the oxygen available to the fire… p495
Closing any openings hinders fire growth until an attack can be planned and established. In general, closing openings helps control the fire unless closing those openings goes against an established incident strategy.
Rapid fire development potential… p495
A growing fire can generate temperatures in excess of structural PPE limits in a few minutes. If the existing ventilation can support fire growth, flashover may occur less than five minutes after ignition. These environments are untenable for occupants and firefighters in full PPE.
When oxygen from ventilation is introduced into the room, the heated gases can quickly reignite, causing rapid fire development. Firefighters and occupants cannot survive rapid fire development conditions.
To prevent rapid fire development from occurring, you must use the appropriate water stream application techniques to cool the heated gases and know how and when to properly release those gases with appropriate ventilation methods and procedures.
Ventilation without coordination will lead to flashover. No amount of additional ventilation will cause the fire to become fuel limited to prevent flashover. The longer the structure or compartment is allowed to ventilate without water being applied, the sooner the flashover occurs… p496
To prevent flashover, ventilation needs to be coordinated with fire attack almost immediately, at the very least within a short amount of time when ventilation alone improves conditions. Ventilation and water application are both necessary to bring a fire under control.
The primary mode of heat transfer from one compartment to another in a structure is from heated gases and smoke movement known as… p497
Convection. This occurs because the natural buoyancy of smoke moves toxic gases and heat from one room to another. If not coordinated, the same ventilation operation changes that the flow path within the structure can move additional heat and smoke to areas not originally involved in the fire.
What best describes how hot fire gases flow during ventilation operations? p497
During ventilation operations, gases flow from interior to exterior because the interior gases, heated by the fire have become less dense.
Gases less dense than air are buoyant, tend to rise, and move toward areas of low pressure. As the less dense, higher pressure, hot gases escape, they create lower pressure that draws in cooler ambient air down low.
Water application to the hot gas layers combined with tactical ventilation can minimize the effect of the new air on fire growth… p498
Water application to the fire compartment begins to transition the fire from vent limited to fuel limited conditions. Vent alone will not achieve this transition.
Tactical ventilation that is implemented during or after fire suppression can create an interior environment or egress path with the following, more tenable conditions… p498
Increased oxygen concentration
Reduced concentration of toxic products of combustion
Reduced temperature levels
Increased visibility to aid in firefighting operations and primary search operations
Firefighters should make two assumptions about any structure fire to guide their decisions when ventilating a structure… p500
The structure itself consists of lightweight construction
The fire in the structure is vent limited
Wind conditions… p500-501
Any opening in a building, whether part of the building design or created by the fire, allows the surrounding atmosphere to affect what is happening inside the building.
Whenever possible, firefighters should use the wind to their advantage during ventilation. Winds as slow as 10mph/15kph can affect structure fire, potentially making them wind driven. If winds at these speeds or faster, firefighters are safest working with the wind to their backs.