What are teh EDG test frequencies?
Monthly - Normal Start - 6 min run Semi Annual - Fast Start 2 Yr - Load Reject Test - EDG DOES NOT TRIP ON LARGEST LOAD 2 YR - AUTO START and load shed 2 Yr - 24hr endurance
What is basis for CCSW limits when running 2/3 EDG?
2/3 EDG CWP discharges to same pipe as U2 CCSW pumps and can choke CWP flow.
If water intake temp less than 82 F, no restrictions
If >82F and <91F, then no more than 3 U2 CCSW pumps operating at same time
IF >91F, then no more than 2 U2 CCS Pps operating
What happens if standby valvues of EDG Voltage and frequency set improperly
may result in failure to autoclose if values too low
Why is EDG INOP when being surveillance tested?
Surveillance testing prevents it from being able tp perform auto emergency design function:
closing of air start cutoff valve during bar over,
lowering speed setpoint for low idle start
EDG tied to grid w/ droop not at 5%
Which conditions require emergency shutdown of EDG?
Loss of Engine cooling
Loss of Engin Oil Pressure
Indication of equipment damage or personnel injury possible
What indications are expected when paralleling DG with another power source?
Higher voltage - will pick up VARS (reactive load) and vice versa
Higher speed - will pick up Watts (Real Load) and vice versa
What is preferred method to secure EDG during emergency stop?
Operate Fuel Rack Lever