RQ-C-4872 (RHR) Flashcards

1
Q

What is the interlock that must be satisfied in order to open IMO-128/ICM-129 (RHR Suction from Loop 2 Hot leg)?

A
  • IMO-128 (NPS-122 < 411#)
  • ICM-129 (NPS-121 < 411#)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What interlock must be satisfied to open ICM-305/306 (RHR Suction from recirc sump)

A
  • IMO-310 (RHR from RWST) & IMO-215 (CTS from RWST) closed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What interlock must be satisfied to open IMO-340/350 (RHR to CCP/SI)

A
  • ICM-305/306 (RHR from recirc sump) open
  • IMO-262 OR IMO-263 (SI mini flow to RWST) closed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What interlock must be satisfied to open IMO-330/331 (RHR to Spray)

A
  • ICM-305/306 (RHR from recirc sump) open
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What interlock must be satisfied to open IMO-310 (RHR from RWST)

A
  • ICM-305/306 (RHR from recirc sump) closed
  • IMO-340/350 (RHR to CCP/SI) closed
  • IMO-330/331 (RHR to Spray) closed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly