RQ-C-4872 (RHR) Flashcards
1
Q
What is the interlock that must be satisfied in order to open IMO-128/ICM-129 (RHR Suction from Loop 2 Hot leg)?
A
- IMO-128 (NPS-122 < 411#)
- ICM-129 (NPS-121 < 411#)
2
Q
What interlock must be satisfied to open ICM-305/306 (RHR Suction from recirc sump)
A
- IMO-310 (RHR from RWST) & IMO-215 (CTS from RWST) closed
3
Q
What interlock must be satisfied to open IMO-340/350 (RHR to CCP/SI)
A
- ICM-305/306 (RHR from recirc sump) open
- IMO-262 OR IMO-263 (SI mini flow to RWST) closed
4
Q
What interlock must be satisfied to open IMO-330/331 (RHR to Spray)
A
- ICM-305/306 (RHR from recirc sump) open
5
Q
What interlock must be satisfied to open IMO-310 (RHR from RWST)
A
- ICM-305/306 (RHR from recirc sump) closed
- IMO-340/350 (RHR to CCP/SI) closed
- IMO-330/331 (RHR to Spray) closed