Containment/Containment Ventilation/Incore Instrumentation (RQ-I-4771) Flashcards

1
Q

What automatically actuates a Containment Ventilation Isolation

A
  • SI
  • Containment Hi Radiation Alarm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which instruments make up the RCS leak detection system

A
  • Sump monitors
  • Radiation monitors
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the cooling medium for Containment Ventilation during closed-loop (normal) operation

A
  • Containment Chilled Water
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

For Containment Purge & Exhaust system which flow rates are designed to be higher (purge or exhaust) and why

A
  • Exhaust flow rates for LOWER containment are higher to minimize the spread of contamination
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which Containment Isolation signal trips the CRDM vent fans

A) Phase A
B) Phase B
C) CVI

A

B) Phase B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How is indicated temperature effected when an RTD shorts vs opens

A
  • Short = Resistance is 0, temperature fails low
  • Open = Resistance is infinite, temperature fails high
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How is indicated temperature effected when an Thermocouple shorts vs opens

A
  • Shorts = Voltage is 0, temperature fails low
  • Open = temperature fails low
How well did you know this?
1
Not at all
2
3
4
5
Perfectly