What is the purpose of the Combined Intermediate Valves (MSR CIV)?
To prevent turbine over speed on a load reject/turbine trip due to residual steam in the MSRs
On a turbine trip which lube oil pumps will be running?
All of them
What is the difference between MWin and MWout
MWin - Maintains constant MW and allows the control valves to modulate
MWout - Maintains constant control valve position and allows MW to fluctuate
What happens if all three Main Turbine Speed pickups fail
If the generator output breakers are OPEN then the turbine trips
When the 10%/20% turbine runback is used on the Turbine HMI how much load is removed?
10%/20% of 100% rated turbine load @ 100 MW/min (i.e., 115/125 MW)
What automatically initiates AMSAC
If 3/4 feedwater flows are less than 25% AND 2/2 impulse pressures are greater than 40%
When AMSAC is actuated what happens
Turbine trips
AFW pumps are started
Flow Conservation initiated
What is the purpose of the MSR
To remove moisture, improve efficiency and protect the LPT blades from erosion