Main Turbine & Turbine Controls (RQ-C-4762) Flashcards

1
Q

What is the purpose of the Combined Intermediate Valves (MSR CIV)?

A

To prevent turbine over speed on a load reject/turbine trip due to residual steam in the MSRs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

On a turbine trip which lube oil pumps will be running?

A

All of them

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the difference between MWin and MWout

A

MWin - Maintains constant MW and allows the control valves to modulate
MWout - Maintains constant control valve position and allows MW to fluctuate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What happens if all three Main Turbine Speed pickups fail

A

If the generator output breakers are OPEN then the turbine trips

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When the 10%/20% turbine runback is used on the Turbine HMI how much load is removed?

A

10%/20% of 100% rated turbine load @ 100 MW/min (i.e., 115/125 MW)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What automatically initiates AMSAC

A

If 3/4 feedwater flows are less than 25% AND 2/2 impulse pressures are greater than 40%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When AMSAC is actuated what happens

A

Turbine trips
AFW pumps are started
Flow Conservation initiated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the purpose of the MSR

A

To remove moisture, improve efficiency and protect the LPT blades from erosion