LOT 203.11 LWPS Flashcards

1
Q
  • LOT 203.11 LWPS*
    • *

The Spent Resin Processing subsystem consists of a High Activity and a Low Activity Spent Resin storage system. What plant demins does each accomodate?

A
  • High Activity:*
  • *CVCS Mixed Beds / Cation Bed**
  • *Recycle Evaporate Feed Demins**
  • *Concentrated Boric Acid Demins**
  • *S/G B/D Demins**
  • Low Activity:*
  • *Boron Thermal Regen Demins**
  • *SFP Demins**
  • *Recycle Evaporator Condensate Demins**
  • Note:*
  • The purpose is to transfer resin w/o generating a lot of liquid waste and to provide decay time before resin is transported offsite for burial.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 203.11 LWPS*
    • *

What are the three methods for processing liquid waste?

A
  • *Filtration**
  • WHT (52’ MAB)*
  • Laundry Hot Shower Tank (10’ MAB) [Dummy]*
  • FDT(52’ MAB) [Dummy]*
  • Condensate Polishing Waste Collection Tank (52’ MAB) [Dummy]*
  • *Demins**
  • WHT Purification Demin (52’ MAB)*
  • LWPS Aux Demin (52’ MAB)*
  • Waste Evaporator Condensate Demin (52’ MAB)*
  • *Evaporation**
  • Not Used at STP*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 203.11 LWPS*
    • *

What water sources drain into the WHT?

A
  • Normal:*
  • *Primary Sample Drains**
  • 100 gpd*
  • *MAB Gravity Drains**
  • Filters / Demins*
  • Alternate:*
  • *RCDT**
  • *Containment Normal Sump**

WHT should only be going up ≈ 100 gpd.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 203.11 LWPS*
    • *

Where are the tanks in the LWPS physically located?

A
  • 10’ MAB South Wall:*
  • *Laundry/Hot Shower Tank (1)**
  • *FDT (1)**
  • *CPRWCT (1)**
  • *WHT (1)**
  • *Waste Evaporator Condensate Tanks (2)**
  • Not Used*
  • *WMTs A/B/C**
  • Vented to their room*
  • Outside MAB South End:*
  • *WMT D/E/F**
  • 4’ FHB:*
  • *LWPS Surge Tanks (2)**
  • Vented to their room*

Pumps are located in areas around tanks

  • Note:*
  • Most tanks in the LWPS including WMT D/E/F are vented plant vent header.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 203.11 LWPS*
    • *

What system does the LWPS use to discharge water?

A

OLACW

CWS

Activity - High on RT-8038 will terminate discharge (FV-4077) and send water back to respective WMT. (Long path recirc)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • LOT 203.11 LWPS*
    • *

What is the difference between an influent tank and an effluent tank?

A
  • Influent Tank:*
  • *Receive waste from system and store it until processed**
  • WHT, LHST, CPRWCT, FDT, Surge Tanks (2)*
  • Effluent Tank:*
  • *Receive processed liquids and store it until released/recycled**
  • WMTs (6)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • LOT 203.11 LWPS*
    • *

What is the function of the WHT?

A

Collects Reactor Grade leakage and other tritiated and aerated water sources

  • Note:*
  • Non-Reactor Grade water goes to Condensate Polishing Regeneration Waste Collection Tank (George Tank)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • LOT 203.11 LWPS*
    • *

For an unprotected outdoor tank, what is activity limited to? (LCO 3.11.1 Liquid Holdup Tanks)

A
  • *≤ 10 Curies**
  • Excludes Tritium and entrained Noble Gases*

LCO N/A to WMT D/E/F b/c they have a berm.

Used for temporary tanks.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • LOT 203.11 LWPS*
    • *

Where does each tank in the LWPS get pumped to?

A
  • WHT:*
  • *FDT (CPRWCT)**
  • Uses Demins/Filters*
  • CPRWCT:*
  • *FDT**
  • Only Strainers*
  • Surge Tanks:*
  • *FDT (CPRWCT)**
  • Only Strainers*
  • LHST:*
  • *WMT C**
  • Only Strainers*
  • FDT:*
  • *WMT D/E/F**
  • Strainers / ALPS*
  • RHTs:*
  • *WMT D/E/F**
  • ALPS*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly