  • LOT 202.38 FHB HVAC*
    • *

What will happen on a FHB HVAC Emergency Operating Actuation Signal?

A
  • Opens:*
  • *Relief Supply Dampers (D-001/D-037)**
  • Relief Damper off closed seat → Main Supply Fans to Trip → D/P Damper (D-138) to Close*
  • *Exhaust Filter Inlet Dampers (D-033/D-034)**
  • *Exhaust Filter Outlet Dampers [Modulates] (D-146/D-147)**
  • Shuts:*
  • *Bypass Line Dampers (D-036/D-162)**
  • Starts:*
  • *ALL (3) Main Exhaust Fans**
  • *ALL (3) Exhaust Booster Fans**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 202.38 FHB HVAC*
    • *

Where does the FHB HVAC exhaust air to?

A

Plant Main Exhaust Stack

Monitored by RT-8035 / RT-8036

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 202.38 FHB HVAC*
    • *

What is pressure in the FHB normally maintained at?

A

Slightly Negative

Minimizes leakage of contaminated air from building to outside air.

Controlled by FHB HVAC DP Control Modulating Damper (FV-9501)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 202.38 FHB HVAC*
    • *

What will cause a FHB HVAC Emergency Operating Actuation Signal?

A

SI

  • *High Radiation (5x10-4 µCi/cc)**
  • RT-8035 OR RT-8036*

High Radiation Signal will drop out after 100 sec (Regardless if High Rad clear) to allow reset on CP-022.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 202.38 FHB HVAC*
    • *

How many fans are normally running at 100% power?

A
  • *2 of 3 Supply Fans**
  • *2 of 3 Exhaust Fans**

Exhaust fans are larger to maintain slightly negative pressure on FHB.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • LOT 202.38 FHB HVAC*
    • *

What will happen to the FHB HVAC system during a LOOP?

A
  • Open:*
  • *Supply Fan Inlet Dampers (D-002/D-003/D-004)**
  • Shut:*
  • *Exhaust Filter Outlet Dampers (D-146/D-147)**
  • Trip:*
  • *Supply Fans**
  • *Exhaust Booster Fans**
  • Starts:*
  • *All (3) Exhaust Fans**
  • Locks in start signal to re-start fans when power returns*

Supply fans will not start on exhaust fan start b/c power will strip and not return.

Operator must open a relief damper (D-001/D-037)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • LOT 202.38 FHB HVAC*
    • *

What will cause a ESF Fail to Actuate alarm on CP022 for the FHB Exhaust filter inlet and outlet dampers? (D-033/D-034 and D-146/D-147)

A
  • Inlet (D-033/D-034):*
  • *D-033/D-034 NOT Open**
  • Outlet (D-146/D-147):*
  • *D-146/D-147 NOT Open**
  • *Air Flow High/Low [2/2]**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • LOT 202.38 FHB HVAC*
    • *

What will auto start/stop a FHB HVAC Supply Fan?

A
  • Auto Start:*
  • *Associated exhaust fan start AND inlet damper FULLY open**
  • Operator must manually open inlet damper*
  • Auto Stop:*
  • *Associated exhaust fan stops**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • LOT 202.38 FHB HVAC*
    • *

How many FHB HVAC exhaust trains must be OPERABLE during movement of irradiated fuel?

A
  • *One Train**
  • *OR**
  • *One Train Capable of being OPERABLE in 2 hrs**

TRM 3.9.12 FHB Exhaust Air System

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  • LOT 202.38 FHB HVAC*
    • *

How are the charcoal beds in the FHB HVAC system protected from fire?

A
  • *Manually activated deluge sprinkler system**
  • Manually activated on CP022 (Fire alarm must be present)*

  • Note:*
  • Fusible link dampers provided for fire barrier isolation*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  • LOT 202.38 FHB HVAC*
    • *

What is the purpose of the FHB tornado damper?

A
  • *Closes on low pressure outside the FHB**
  • Prevents crushing ducting inside FHB during Tornado*

Located on South side of MAB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  • LOT 202.38 FHB HVAC*
    • *

What cools the components in the FHB HVAC System?

A
  • MAB Chill Water:*
  • *FHB HVAC Supply**
  • *Temporary FHB Supplemental Cooling AHU**
  • Only used to reduce heat during cask loading*
  • Essential Chill Water:*
  • *ECCS Pump Room**
  • *Recirc Valve Room**
  • *SF Pump Room**
  • TSC Chill Water:*
  • *PASS Station**