LOT 202.38 FHB HVAC Flashcards
- LOT 202.38 FHB HVAC*
- *
What will happen on a FHB HVAC Emergency Operating Actuation Signal?
- Opens:*
- *Relief Supply Dampers (D-001/D-037)**
- Relief Damper off closed seat → Main Supply Fans to Trip → D/P Damper (D-138) to Close*
- *Exhaust Filter Inlet Dampers (D-033/D-034)**
- *Exhaust Filter Outlet Dampers [Modulates] (D-146/D-147)**
- Shuts:*
- *Bypass Line Dampers (D-036/D-162)**
- Starts:*
- *ALL (3) Main Exhaust Fans**
- *ALL (3) Exhaust Booster Fans**
- LOT 202.38 FHB HVAC*
- *
Where does the FHB HVAC exhaust air to?
Plant Main Exhaust Stack
Monitored by RT-8035 / RT-8036
- LOT 202.38 FHB HVAC*
- *
What is pressure in the FHB normally maintained at?
Slightly Negative
Minimizes leakage of contaminated air from building to outside air.
Controlled by FHB HVAC DP Control Modulating Damper (FV-9501)
- LOT 202.38 FHB HVAC*
- *
What will cause a FHB HVAC Emergency Operating Actuation Signal?
SI
- *High Radiation (5x10-4 µCi/cc)**
- RT-8035 OR RT-8036*
High Radiation Signal will drop out after 100 sec (Regardless if High Rad clear) to allow reset on CP-022.
- LOT 202.38 FHB HVAC*
- *
How many fans are normally running at 100% power?
- *2 of 3 Supply Fans**
- *2 of 3 Exhaust Fans**
Exhaust fans are larger to maintain slightly negative pressure on FHB.
- LOT 202.38 FHB HVAC*
- *
What will happen to the FHB HVAC system during a LOOP?
- Open:*
- *Supply Fan Inlet Dampers (D-002/D-003/D-004)**
- Shut:*
- *Exhaust Filter Outlet Dampers (D-146/D-147)**
- Trip:*
- *Supply Fans**
- *Exhaust Booster Fans**
- Starts:*
- *All (3) Exhaust Fans**
- Locks in start signal to re-start fans when power returns*
Supply fans will not start on exhaust fan start b/c power will strip and not return.
Operator must open a relief damper (D-001/D-037)
- LOT 202.38 FHB HVAC*
- *
What will cause a ESF Fail to Actuate alarm on CP022 for the FHB Exhaust filter inlet and outlet dampers? (D-033/D-034 and D-146/D-147)
- Inlet (D-033/D-034):*
- *D-033/D-034 NOT Open**
- Outlet (D-146/D-147):*
- *D-146/D-147 NOT Open**
- *Air Flow High/Low [2/2]**
- LOT 202.38 FHB HVAC*
- *
What will auto start/stop a FHB HVAC Supply Fan?
- Auto Start:*
- *Associated exhaust fan start AND inlet damper FULLY open**
- Operator must manually open inlet damper*
- Auto Stop:*
- *Associated exhaust fan stops**
- LOT 202.38 FHB HVAC*
- *
How many FHB HVAC exhaust trains must be OPERABLE during movement of irradiated fuel?
- *One Train**
- *OR**
- *One Train Capable of being OPERABLE in 2 hrs**
TRM 3.9.12 FHB Exhaust Air System
- LOT 202.38 FHB HVAC*
- *
How are the charcoal beds in the FHB HVAC system protected from fire?
- *Manually activated deluge sprinkler system**
- Manually activated on CP022 (Fire alarm must be present)*
- Note:*
- Fusible link dampers provided for fire barrier isolation*
- LOT 202.38 FHB HVAC*
- *
What is the purpose of the FHB tornado damper?
- *Closes on low pressure outside the FHB**
- Prevents crushing ducting inside FHB during Tornado*
Located on South side of MAB
- LOT 202.38 FHB HVAC*
- *
What cools the components in the FHB HVAC System?
- MAB Chill Water:*
- *FHB HVAC Supply**
- *Temporary FHB Supplemental Cooling AHU**
- Only used to reduce heat during cask loading*
- Essential Chill Water:*
- *ECCS Pump Room**
- *Recirc Valve Room**
- *SF Pump Room**
- TSC Chill Water:*
- *PASS Station**