LOT 201.13 ECW Flashcards
- LOT 201.13 ECW*
- *
What will auto start the screen wash booster pump?
- Auto Start:*
- *SI**
- *Traveling Screens Start**
Must be manually secured.
MCC switch in LOCAL eliminates ALL Auto Functions.
- Note:*
- Starting screen wash booster pump will auto open screen wash valve unless MCR switch in close.*
- LOT 201.13 ECW*
- *
What will auto start/stop the ECW pump room ventilation fans?
- Auto Start: (Both Fans)*
- *ECW Pump Room Temp - High (94 ˚F)**
- *ECW Pump Start**
- Auto Stop: (Both Fans)*
- *ECW Pump Room Temp < 94 ˚F**
Max temp is 104 ˚F
- Note:*
- If fan started due to ECW pump start, then fans must be manually secured. (Locally / CP022)*
- LOT 201.13 ECW*
- *
What does the accident analysis assume for the ECW system?
Loss of 1 train in both units
LOOP
Normal Operation: 2 Trains of ECW and 1 Train of CCW
- Note:*
- 2 Trains of ECW required for EAB HVAC requirements.*
- LOT 201.13 ECW*
- *
What will auto start/stop the ECW traveling screens?
- Auto Start:*
- *SI**
- *High Screen D/P (5.5”) w/ Sreen Wash Pressure ≥ 63 psig**
- Resets at 4.5” (Will run for 4 mins after reset)*
- Auto Stop:*
- *Sreen Wash Pressure < 63 psig**
- N/A for SI*
- *∆Level < Setpoint**
- LOT 201.13 ECW*
- *
Describe what happens to the ECW blowdown valves when a SI occurs?
- *Blowdown valves shut**
- Once SI clears, must take valves to shut then back to auto on CP002*
CP002 switch in AUTO:
- ECW Train 2A: Valve opens
- ALL other ECW Trains: Cycles Open/Shut with ECW pump starting/securing
Valve physically located on MAB 10’ at ECW Sump. (No local switch)
Note:
By procedure, every blowdown valve with exception of train 2A is maintained in the CLOSE position on CP002
- LOT 201.13 ECW*
- *
What will happen in the ECW system once a ECW pump is started?
Starts self cleaning strainer motor
- *Starts to Open Discharge Valve after 10 sec**
- If not open after 25 sec, pump trips (N/A for SI)*
Opens chemical injection valve for associated bay
- *Opens Blowdown Valves (N/A for train 2A)**
- Maintain CP002 switches in CLOSE so doesn’t really happen*
- *Starts ventilation fans**
- Must be manually secured*
- Discharge Valve MCC switch in local prevents discharge valve opening when ECW pump starts.
- Self Cleaning strainer does not have switch in MCR.
- Note:*
- Discharge valve will shut 2 mins after ECW pump secures to prevent draining ECW piping to ECW pond and thus preventing water hammer on pump S/U.*
- LOT 201.13 ECW*
- *
What loads does ECW supply?
Essential Chillers
- ESF DGs:*
- *Jacket Water HX**
- *Turbo Charger Combustion Air Cooler**
- *Lube Oil HX**
- CCW:*
- *CCW HX**
- *CCW Pump Supplementary Cooler**
- Cools area cooler and CCW pump motor*
- LOT 201.13 ECW*
- *
What will cause a CCW standby train not selected alarm on CP002?
2 ECW/CCW train selector switches in “OFF”
- LOT 201.13 ECW*
- *
What MCCs are located in the ECW intake structure?
MCC E1A3
MCC E1B3
MCC E1C3
- LOT 201.13 ECW*
- *
What lubricates the ECW pump bearings?
Water being pumped flows across the bearings on it’s way up the pump column
- LOT 201.13 ECW*
- *
What is the DBA for the ECW pond embankments?
- North Embankment:*
- *Colorado River Dam Failures**
- South Embankment:*
- *Break in Cooling Resevoir**
- LOT 201.13 ECW*
- *
Does ECW flow the tubes or the shell of the CCW HX?
Tubes
Minimizes debris in the shell of HX
- Note:*
- CCW is a higher pressure than ECW.*
- LOT 201.13 ECW*
- *
What components in the ECW system have a Bypass/Inop alarm on CP002?
- ECW Pump:*
- *Pump** (CP002/MCC)
- *Discharge MOV** (CP002/MCC)
- *Strainer** (MCC only)
- Traveling Screen:*
- *Pump** (CP002/MCC)
- *Discharge Valve** (CP002/MCC)
- *Traveling Screen** (CP002/MCC)
- Ventilation:*
- *Fans** (CP022/MCC)
- LOT 201.13 ECW*
- *
What provides makeup to the ECW pond?
- Normal:*
- *Well Water**
- Alternate:*
- *Unit 2 ECW Sump via ECW 2A return line**
- Unit 1 Sump is normally aligned to Unit 1 CW Return.
- Unit 2 Sump can be aligned to Unit 1 CW Return.
- Note:*
- ECW Sump located on MAB 10’ in Essential Chiller Train C Room.*
- LOT 201.13 ECW*
- *
What is the minimum level and temperature of the ECW pond as required by LCO 3.7.5 Ultimate Heat Sink?
- Level:*
- *≥ 25.5 ft**
- Max Level 26 ft (FSAR)*
- Temperature:*
- *≤ 99 ˚F**
Pond sized to have a 30 day cooling water supply to safely shutdown and cooldown both Units while maintaining a heat sink for heat removal
- Note:*
- ECW Bay LVL indication and alarms located on CP002
- ECW Bay LVL - Low 2 (14.96 ft) for LCO 3.7.5 entry.