LOT 202.36 Essential Chilled Water Flashcards
- LOT 202.36 Essential Chilled Water*
- *
Where is the essential chilled water expansion tank physically located?
- *MAB 26’**
- CCW HX Room*
Pressurized with N2 (26 - 30 psig) for NPSH
- Still OPERABLE if expansion tank at Patm
- *
- Note:*
- Unlike level control which is a manual valve, the N2 pressure control valve is a self-actuated pressure regulator valve.*
- LOT 202.36 Essential Chilled Water*
- *
What system fills the essential chilled water expansion tank?
Demin Water
Filled with manual valve. (+5” - +12”)
- LOT 202.36 Essential Chilled Water*
- *
What AHUs in the FHB are supplied by Essential Chilled Water?
SFP AHU
Containment Sump Isolation Valve AHU
ESF pump cubicles AHU
- LOT 202.36 Essential Chilled Water*
- *
What permissives must be met in order for the essential chillers to sequence onto the ESF DGs?
- *Chill Water Outlet Temp ≥ 38 ˚F**
- Resets at 39 ˚F*
- *Chill Water D/P across evaporator HX ≥ 5 psid**
- 5 psid [5 sec TD] / Reset at 7 psid*
Chill Water pump breaker shut
- LOT 202.36 Essential Chilled Water*
- *
What spaces in the EAB are cooled by Essential Chilled Water?
EAB Main Supply
- *EAB Pen Space**
- Cooled by Emergency MAB AHU located in MAB*
CRE
- LOT 202.36 Essential Chilled Water*
- *
How many trains of essential chilled water is normally in operation?
2 Trains
LCO 3.7.14 Essential Chilled Water Loops requires 3 trains to be OPERABLE in MODES 1 -4.
- Note:*
- Due to 2 trains of EAB HVAC in operation*
- LOT 202.36 Essential Chilled Water*
- *
What cools the essential chillers?
ECW
- LOT 202.36 Essential Chilled Water*
- *
What ECW pond temperature would make the Essential Chilled Water system inoperable?
< 41 ˚F
Per POP02, declare inoperable in MODES 1 - 4.
- LOT 202.36 Essential Chilled Water*
- *
What powers the essential chillers and the essential chilled water pumps?
- Essential Chillers:*
- *E1A / E1B / E1C**
- Essential Chilled Water Pumps:*
- *MCC E1A1 / E1B1 / E1C1**
- LOT 202.36 Essential Chilled Water*
- *
What AHUs in the MAB are supplied by Essential Chilled Water?
Essential Chiller Room
Rx Makeup Water Cubicle
Boric Acid Transfer Pumps Cubicle
CVCS Valves Room
CVCS Pump Room
Radiation Monitoring Room
- LOT 202.36 Essential Chilled Water*
- *
When will the running and standby essential chillers start on a LOOP / SI? (ESF DG Sequencer)
- Standby:*
- *35 sec**
- (Chilled Water Pump / Chiller Oil Pump)*
- *65 sec (30 sec prelube cycle)**
- Essential Chiller*
- Running:*
- *240 sec**
- (Chilled Water Pump / Chiller Oil Pump)*
- *270 sec (30 sec prelube cycle)**
- Essential Chiller*
Running essential chiller must complete 135 sec post lube cycle before it can be restarted on ESF DG sequencer.
Note:
ESF sequencer bypasses the 30 min anti-recycle timer permissive
- LOT 202.36 Essential Chilled Water*
- *
How do the pre-rotation vanes and hot gas bypass work?
- Pre-Rotation Vanes:*
- *Control chill water temp from 10% - 100%**
- *Temp↑ Vanes open**
- *Temp↓ Vanes close**
- Hot Gas Bypass:*
- *When Vanes 10% open control shifted to Hot Gas Bypass**
- *Sends hot gas from condenser to evaporator**
- *Once Hot gas bypass full open control shifted back to vanes**
- *Vanes will then close**
Vanes and hot gas bypass will not move for 4 minutes on startup to prevent oil foaming.