LOT 202.36 Essential Chilled Water Flashcards

1
Q
  • LOT 202.36 Essential Chilled Water*
    • *

Where is the essential chilled water expansion tank physically located?

A
  • *MAB 26’**
  • CCW HX Room*

Pressurized with N2 (26 - 30 psig) for NPSH

  • Still OPERABLE if expansion tank at Patm
    • *
  • Note:*
  • Unlike level control which is a manual valve, the N2 pressure control valve is a self-actuated pressure regulator valve.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What system fills the essential chilled water expansion tank?

A

Demin Water

Filled with manual valve. (+5” - +12”)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What AHUs in the FHB are supplied by Essential Chilled Water?

A

SFP AHU

Containment Sump Isolation Valve AHU

ESF pump cubicles AHU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What permissives must be met in order for the essential chillers to sequence onto the ESF DGs?

A
  • *Chill Water Outlet Temp ≥ 38 ˚F**
  • Resets at 39 ˚F*
  • *Chill Water D/P across evaporator HX ≥ 5 psid**
  • 5 psid [5 sec TD] / Reset at 7 psid*

Chill Water pump breaker shut

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What spaces in the EAB are cooled by Essential Chilled Water?

A

EAB Main Supply

  • *EAB Pen Space**
  • Cooled by Emergency MAB AHU located in MAB*

CRE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • LOT 202.36 Essential Chilled Water*
    • *

How many trains of essential chilled water is normally in operation?

A

2 Trains

LCO 3.7.14 Essential Chilled Water Loops requires 3 trains to be OPERABLE in MODES 1 -4.

  • Note:*
  • Due to 2 trains of EAB HVAC in operation*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What cools the essential chillers?

A

ECW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What ECW pond temperature would make the Essential Chilled Water system inoperable?

A

< 41 ˚F

Per POP02, declare inoperable in MODES 1 - 4.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What powers the essential chillers and the essential chilled water pumps?

A
  • Essential Chillers:*
  • *E1A / E1B / E1C**
  • Essential Chilled Water Pumps:*
  • *MCC E1A1 / E1B1 / E1C1**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  • LOT 202.36 Essential Chilled Water*
    • *

What AHUs in the MAB are supplied by Essential Chilled Water?

A

Essential Chiller Room

Rx Makeup Water Cubicle

Boric Acid Transfer Pumps Cubicle

CVCS Valves Room

CVCS Pump Room

Radiation Monitoring Room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  • LOT 202.36 Essential Chilled Water*
    • *

When will the running and standby essential chillers start on a LOOP / SI? (ESF DG Sequencer)

A
  • Standby:*
  • *35 sec**
  • (Chilled Water Pump / Chiller Oil Pump)*
  • *65 sec (30 sec prelube cycle)**
  • Essential Chiller*
  • Running:*
  • *240 sec**
  • (Chilled Water Pump / Chiller Oil Pump)*
  • *270 sec (30 sec prelube cycle)**
  • Essential Chiller*

Running essential chiller must complete 135 sec post lube cycle before it can be restarted on ESF DG sequencer.

Note:
ESF sequencer bypasses the 30 min anti-recycle timer permissive

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  • LOT 202.36 Essential Chilled Water*
    • *

How do the pre-rotation vanes and hot gas bypass work?

A
  • Pre-Rotation Vanes:*
  • *Control chill water temp from 10% - 100%**
  • *Temp↑ Vanes open**
  • *Temp↓ Vanes close**
  • Hot Gas Bypass:*
  • *When Vanes 10% open control shifted to Hot Gas Bypass**
  • *Sends hot gas from condenser to evaporator**
  • *Once Hot gas bypass full open control shifted back to vanes**
  • *Vanes will then close**

Vanes and hot gas bypass will not move for 4 minutes on startup to prevent oil foaming.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly