LOT 203.07 Demin Water Flashcards

1
Q
  • LOT 203.07 DWS*
    • *

What will auto start/stop the DWS Transfer pumps?

A
  • Auto Start:*
  • *Lead Pump: DWS Header Pressure 97.5 psig**
  • *Lag Pump: DWS Header Pressure 93 psig**
  • Auto Stop:*
  • *Lead Pump: DWS Header Pressure 128 psig**
  • *Lag Pump: DWS Header Pressure 125 psig**
  • Placing switch in “MAIN” will start pump if DWST Level > 2.75’
  • DWST Level > 2.75’ is a pump permissive for ALL pump starts.
  • Note:*
  • System has 3 transfer pumps*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 203.07 DWS*
    • *

What alarms are available in the MCR for the DWS?

A

Pump Trouble on CP009

  • Loss of control power
  • Thermal overload
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 203.07 DWS*
    • *

What is the usable capacity of the DWST?

A

961,700 gal

Enough capacity to supply both units for 2 days

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 203.07 DWS*
    • *

How do we control corrosion in the DWST?

A

Plastite is bonded to metal of the tank

N2 blanket

How well did you know this?
1
Not at all
2
3
4
5
Perfectly