LOT 201.08 BTRS Flashcards

1
Q
  • LOT 201.08 BTRS*
    • *

What is the flowrate through the BTRS Demins?

A

40 - 120 gpm

40 gpm basis:

  • Proper flow distributor operation and prevent channeling

120 gpm basis:

  • Prevent channeling
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 201.08 BTRS*
    • *

When will the letdown temperature divert valve (TCV-143) automatically bypass the BTRS demins?

A

BTRS Demin Inlet Temp - High (157 ˚F)

Located on CP004

  • Note:*
  • Loss of Air/voltage fails to divert.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 201.08 BTRS*
    • *

What is the limiting temperature and component for the BTRS?

A

130 ˚F

RCP Seals

Limit temperature to 115 ˚F to allow CCPs to add 15 ˚F.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 201.08 BTRS*
    • *

Which way is flow sent through the BTRS demins to dilute the RCS?

A

Down through demins

Sending water up through demins will borate. (Not Done)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 201.08 BTRS*
    • *

What is the flowpath of the BTRS system?

A

Moderating HX
Letdown Chiller
No cooling water
Letdown Reheat
No cooling water
Demins
Moderating HX

How well did you know this?
1
Not at all
2
3
4
5
Perfectly