AUC 5 Flashcards
5
TorF lofts can not be converted in MD’s, 2 unit max.
The artist in residence sign is how big? What size letters? How high is it placed? Where is it placed? What is info is on the top line, middle line and bottom line?
True, cannot be converted in MD’s, 2 unit max
Sign is 8x10” with 2” black letters on white background.
Placed 7’ above sidewalk level as close as possible to main entrance on front wall.
Top Line - A.I.R (artist in residence)
Middle line - will be what floor (ex 3F is 3rd floor not apt 3F)
Bottom line- location in building (ex R is rear)
Auc5
When construction reaches a working deck of how high a standpipe is required to be in state of readiness and painted ____.
Buildings being demo’d standpipes shall be (wet/dry), and capped where?
Working deck reaches 75’ and painted red
Dry and capped above the outlet on floor below floor being demolished
Auc5
When is a standpipe needed for below grade?
TorF dry standpipe during demo or alteration requires air pressurized system
All exposed sprinkler piping must be painted ____? What color for exposed standpipe piping?
Below ground needed when depth is greater than 75’
True dry standpipe needs air pressurized system
All exposed sprinkler and standpipe piping is painted red
*valve are colored, red- standpipe, green-sprinkler, yellow-combination
Auc5
During construction one permanent stair is brought to a distance within __ft or __floors below working deck
1 elevator or hoist must be within __ft or __floors of working deck
Permanent stair within 40ft or 4 floors of working deck
1 elevator or hoist within 75ft or 7 floors of working deck
Auc 5
When do you serve a summons for a patio fireplace?
Outdoor gas appliance, how far from emergency shut off? From building? From decorations, from exit, from fire extinguisher?
Can furniture be within 5 ft?
Summons for chronic problem, one time call just extinguish it
Outdoor gas appliance 5ft from emergency shut off, 5ft from building, 5ft from decorations, 5ft from exit, fire extinguisher 10-20ft away.
Furniture can be within 5ft if it has flame retardant coating
Auc5
Outdoor BBQ at residential places the grate area can be no more than __sq/ft. Not to be used used within __ft of any combustible material, not within __ft of doors and windows.
Apartments can have # of LPG containers that are ___(size in lb or oz)
10sq/t or 10ft for BBQ’s
Apartments can have a max of 4 16.4oz containers
Auc5
TorF
1 or 2 family dwellings can have LPG containers of what size?
Where can 20lb containers not be stored?
How many 20lb containers can they have?
How many 16.4oz containers can they have, can they be stored indoors?
1 or 2 family dwellings can have 20lb or 16.4oz LPG containers
20lb cannot be stored indoors, on roofs, or balcony’s
2 20lb tanks max
4 16.4oz containers can be stored indoors
Auc5
Storage must be maintained __ft below ceilings if no sprinklers.
__” if sprinklers.
Storage must be maintained 2ft below ceilings is no sprinklers, 18” if sprinklers
Auc5
Rooftop conduit piping colors:
Red, orange, yellow, yellow with black stripes, yellow with labels at regular intervals.
Red- high voltage Orange - low voltage Yellow - natural gas Yellow w/black stripes - fuel oil Yellow labeled at regular intervals - other compressed gas
Auc5
Rooftop conduit piping, what are the colors for:
High voltage, low voltage, natural gas, fuel oil, other compressed gasses
High voltage - red Low voltage - orange Fuel oil - yellow with black stripes Natural gas - yellow Other compressed gas - yellow with labels at regular intervals
Auc 5
When more then # apts per floor what does the elevator lobby need?
Apartments are labeled within __” of the bottom of the door.
How much flammable liquids are allowed in basements or cellars? Combustible liquids?
8 apts per floor or more need sign with arrow pointing to all apartments in each direction
Apts labeled within 12” of bottom of door
No amounts of flammable liquids stored in basements or cellars
Combustible liquids allowed if sprinklered
*if established before 2008 they can store flammable liquids
Auc5 Color coding at bulk plants? Standpipe/ yard hydrant system Automatic sprinklers Non-automatic sprinklers CO extinguishing systems Steam extinguishing systems Foam extinguishing systems
Standpipe/ yard hydrant system - red with white bands
Automatic sprinklers- red with green bands
Non-automatic sprinklers- red with aluminum bands
CO extinguishing systems- red with brown bands
Steam extinguishing systems - red with black bands
Foam extinguishing systems - red with orange bands
Auc5 LPG storage What do you do for illegal storage? Permit allows how much storage? Containers more then \_\_lb can only be moved to different floor via elevator. Containers \_\_lb or less can be moved via stairs or elevator. And has to be under supervision of C of F holder
Illegal storage is summons and confiscation
Permit allows 400 standard cubic feet or 46 lbs
Containers more than 20 pound by elevator only, 20lb or less can use stair or elevator if stairwell is unoccupied
Auc5
When does notification to the FD have to be made when a standpipe is OOS? What about for sprinkler or fire alarm systems?
Any time the standpipe is OOS a notification to FD must be made.
Sprinkler or alarm system OOS notification made when:
1-either system OOS on more than1 floor
2-sprinkler system repairs cannot be completed within 8hrs
3-fire alarm OOS for more than 8hrs in any 24hr period
4-when either system is OOS and another system will be OOS
Auc5
TorF summons for failure to notify of OOS fire protection system?
If fire protection system is OOS the impairment coordinator or trained staff can do fire watch for 1st __hrs if each floor is patrolled at leave once an hour and area doesn’t exceed 50,000sq/ft
True summons for failure to notify
For 1st 4 hours