AP-9 (loss of inst air) Flashcards
1
Q
AP-9
What are the major actions catagories to Loss of instrument Air?
A
- Stabilize plant
- Alert personnel
- Restore inst air hdr press
- Identify leak location
- Isolate leak
2
Q
AP-9
What conditions during loss of instrument air will warrent a Rx trip?
A
If the following cannot be controlled in their normal operating bands:
- L s/g
- L pzr
- P pzr
3
Q
AP-9
Why should long term use as Service air as a backup source be avoided?
A
prevent contamination of Instrument Air from Service air
4
Q
AP-9
What are the major actions associated W/ appx B.
A
Achieve & Maintain HSBY w/ Rx trip and loss inst air
- Maintain Tavg w/ 10% stm dmps
- Maintain Lpzr with CCP
- Secure Sec plant
- close MSIV’s
- trip MFW
- Recirc cond thru polisher
- Maintain HSBY