AP-9 (loss of inst air) Flashcards

1
Q

AP-9

What are the major actions catagories to Loss of instrument Air?

A
  • Stabilize plant
  • Alert personnel
  • Restore inst air hdr press
  • Identify leak location
  • Isolate leak
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

AP-9

What conditions during loss of instrument air will warrent a Rx trip?

A

If the following cannot be controlled in their normal operating bands:

  • L s/g
  • L pzr
  • P pzr
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

AP-9

Why should long term use as Service air as a backup source be avoided?

A

prevent contamination of Instrument Air from Service air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

AP-9

What are the major actions associated W/ appx B.

A

Achieve & Maintain HSBY w/ Rx trip and loss inst air

  • Maintain Tavg w/ 10% stm dmps
  • Maintain Lpzr with CCP
  • Secure Sec plant
    • close MSIV’s
    • trip MFW
    • Recirc cond thru polisher
  • Maintain HSBY
How well did you know this?
1
Not at all
2
3
4
5
Perfectly