AP-5 (malf of eagle 21 or control channel) Flashcards
1
Q
What are the entry conditions for AP-5 (eagle 21 or control system malfunction)?
A
- PPS CHANNEL SET FAILURE (PK06‑01)
- PPS RTD FAILURE (PK06‑03)
- PPS TROUBLE (PK06‑04)
- PROCESS CONTROL SYS TROUBLE (PK06‑21)
- Control system not functioning properly
- Spurious control actions not consistent with plant or equipment operating state
- indication descrepency > 5% for multiple parameters monitoring same parameter (except Lpzr, 8.5% allowed)
2
Q
What must be “positively identified” to make utilizing AP-5 (eagle 21/ PCS malf) appropriate?
A
It assumes that any abnormal indication or control transient has been POSITIVELY IDENTIFIED as a result of a protection rack or instrument failure and not as a result of an actual emergency situation.
3
Q
When in AP-5 (eagle 21 or PCS malf) and bistables need to be tripped, who authorizes and performs tripping of bistables?
A
Prepared - SFM
Authorized - SM
Performed - I & C Tech