AP-19 (Malf of Rx MU cntrl) Flashcards

1
Q

AP-19

What inputs does LT-112 feed into?

What happens if LT-112 fails high?

What happens if LT-112 fails low?

A

LT-112 outputs

  • auto m/u (14% -> 24%)
  • charging suct xfr -> RWST (1/2 chnl)
  • trip open LCV-112A (87%, also alarm)
  • ind (VB 2)

fails high

  • LCV-112A opens => Lactual goes down
  • no m/u
  • empties VCT (no swap to RWST)
  • lose CCP’s

fails low

  • auto m/u => Lactual goes up
  • LCV-112A modulates open (based on LT-114)
  • m/u overpowers LCV-112A (100 > 75 gpm)
  • VCT goes solid (relieves to LHUT)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

AP-19

What inputs does LT-114 feed into?

What happens if LT-114 fails high?

What happens if LT-114 fails low?

A

LT-114 inputs

  • modulates open LCV-112A
  • CCP suction xfr -> RWST
  • indication (VB 2 and HSDP)

Fails high

  • LCV-112A modulates open => Lactual goes down
  • auto m/u at 14% => Lactual goes up
  • when m/u stops @ 24% => Lactual goes down
  • Lactual will cycle between 14 and 24%

Fails low

  • Low VCT alarm, Lactual will not move
  • half channel made up to xfr CCP suction to RWST
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

AP-19

What will give you a m/u deviation alarm?

What happens when you get this alarm to m/u control system?

A

Boric acid flow >/= 1.5 gpm from flow setpoint for 30 sec

Primary wtr flow >/= 8 gpm from flow setpoint for 30 sec

if m/u controller not in manual FCV’s 110A, B, 111A, B all go closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

AP-19

What will LT-112 indicate if a rupture in the reference leg occurs?

What will LT-114 indicate if a rupture in the variable leg occurs?

A

reference leg break = indicates high

variable leg break = indicates low

level = D/P, => D/P up, Level up

D/P = Pvar - Pref

How well did you know this?
1
Not at all
2
3
4
5
Perfectly