AP-30 (Mn. Gen Malf) Flashcards
1
Q
AP-30 (Mn Gen Malf)
Per FOP what is the Unit trip criteria?
A
Bottom or Top stator coil delta T > 21 F
individual stator T/C > 193 F
GCM alarm w/
- stator temp alarm
- exciter ground alarm
- turb gen vib
- RF alarm
RF alarm w/
- stator temp alarm
- exciter ground alarm
- turb gen vib or rise in temp
- GCM alarm
Generator voltage unstable and cannot be controlled
Seal oil cooler outlet temp > 125 deg F for 15 min
Gen H2 pressure lowering uncontrollably
Gen liquid level high and Defoaming tnk level high
H2 / seal oil DP not kept > 3 psig
2
Q
(AP-30 Mn Gen Malf)
What are the sections to AP-30?
A
A - Generator Condition Monitor
B - Exciter Ground
C - Exciter Trouble
D - Generator Trouble
E - Generator Seal Oil Trouble
F - Generator H2 system Trouble
G - Stator wtr cooling system Trouble