Precourse Quiz 1 Flashcards
What will auto start a DG?
UV or SI
How long does the DG have to be loaded on a bus?
10 seconds
What will trip a DG regardless of how it started?
Overspeed (660 rpm)
Generator differential current
Emergency Stop Pushbutton
What are the pressure trips on a DG in test mode?
Low lube oil pressure 30 psig
Low turbocharger oil pressure 30 psig
High crankcase pressure 0.5 psig
What is the design bases for the DG?
Loaded onto the bus in 10 seconds
7 days of fuel
If blackout in one unit, other unit DG can provide safe shutdown power for 4 hours
When do Fuel Oil XFR pumps starts?
Both start when DG >280 rpm
One starts when low tank level 14” above centerline
What will trip DG output breaker on UV start?
F Loss of field
U Underfrequency
R Reverse Power
N neutral overcurrent
D Gen Diff current
Overcurrent relay
S SAT feed BRKR lockout
E Stop PB
What will trip the DG output breaker on an SI start?
Differential current
Manual
After a DG start when does the CV pump sequence on?
0 seconds
Where are the DG sequencers powered from?
SARA DC 111
SARB DC 112
A sequencer timer AC 111
B sequencer timer AC 114
What are the DG ratings?
Continuous 5500 KW 954A
2000 hours 5935KW 1030A
2/24 6050KW 1050A
What is the difference between droop and isochronous mode on DG?
In iso mode governor maintains speed constant regardless of load
In droop speed lowers as load rises
What is the pressurizer heat-up limit?
100F/hr
What is the pressurizer cooldown limit?
200F/hr
What is the differential temperature limit between RCS and PZR spray?
320F
What is the capacity and lift setpoint of a pressurizer PORV?
RY456 210,000 lbm/hr 2335 psig
RY455A 210,000 lbm/hr 2345 psig
What is the capacity and lift setpoint of a pressurizer safety valve?
420,000 lbm/hr 2460 psig
What is the program level band for the pressurizer and what is it controlled by?
Unit 1 25-60% 557-587F Tave
Unit 2 27-60% 557-581F Tave
Constant mass: Level is designed to vary with RCS temperature (using auctioneered 2nd highest Tave) with no mass addition or loss
Controlled by charging and letdown flows
How many sets of pressurizer heaters are there?
4 sets,C proportional ABD backup
What is the capacity of the pressurizer heaters?
Proportional C 400KW
Backup ABD 1400KW
What are the power supplies for pressurizer heaters?
A&D 143
B&C 144
What allows the PORVs to operate once air is isolated to containment?
They have their own accumulators and each accumulator will allow its associated PORV to cycle 50 times
What are the pressurizer level setpoints?
92% PZR high level Rx trip 2/3
70% High level alarm
60% 100% program level
25/27% 0% power program level
17% PZR heaters de-energized
+5% >Band backup heaters energize regardless of level
-5% low level alarm
What is the hydrostatic test pressure for pressurizer?
3107 psig