Exam 8 Review questions Flashcards

1
Q

At what suction pressure do the AF pumps trip?

A

16.5 psia

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

At what suction pressure do the AF pumps swap from CST to SX?

A

18.1 psia

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the relationship between AF005s and AC/DC/IA?

A

On a loss of DC they fail open. On a loss of IA they fail open. On a loss of AC 111 or 114 they fail closed because demand signal goes to 0%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the effect of losing the SX system while both AF pumps are running?

A

The ‘A’ pump will trip but the ‘B’ will keep running because it has an SX booster pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the loads on bus 157?

A

1A and 1C HDP, 1A RCP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the 6.9 kv bus undervoltage scheme?

A

At <5268 V on 2/4 busses; AF pumps start and reactor trip if above P-7. At <4920V all load breakers will get stripped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the setpoint of the 6.9 kv bus underfrequency scheme?

A

<57 Hz on 2/4 busses will trip all running RCPs and generate reactor trip if above P-7.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where are the 6.9 kv busses underfrequency relays powered from and in what scenario would they not actuate?

A

The underfrequency relays are powered from the 6.9 kV bus itself and will actuate if frequency is degrading but will not actuate if the bus loses power instantaneously.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the TDFWP trips?

A

Overspeed at 5720 rpm. Low EH pressure <1000 psig. Low vacuum <14” HgA. Manual PB or Ovation button. Local EH handle. Both HP and LP stop valves closed. P-14. SI. Low lube oil <10 psig.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the CD/CB pump trips?

A

P.L.U.G. Phase OC - Low lube oil <4.3 psig - Undervoltage - Ground OC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the various containment pressure setpoints?

A

3.4 psig 2/3 actuates SI. 8.2 psig 2/3 MSI. 20.0 psig 2/4 Phase B and CSAS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly