Pre-course ILT CS Flashcards

1
Q

What conditions will initiate a CS actuation?

A

Containment Hi-3 >20psig 2/4
Manual 2/2 @ 1/2 locations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What happens on an auto actuation of CS?

A

CS007 Pump Discharge Opens
CS019 Eductor Suction Opens
CS Pump starts after Eductor Suction opens
CS010 Eductor Iso valve gets confirmation signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the CS pump auto start interlocks?

A

C/S in A/T or A/C
CS019 eductor suction open
Cntmnt Hi-3 at 20 psig 2/4 OR manual 2/2 switches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

CS

A
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CS pump Test Start interlocks?

A

C/S in close position
CS007 Closed
CS040 Closed
SI001 Open
Test Switch in “TEST”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly