What will auto start a DG?
UV or SI
How long does the DG have to be loaded on a bus?
10 seconds
What will trip a DG regardless of how it started?
Overspeed (660 rpm)
Generator differential current
Emergency Stop Pushbutton
What are the pressure trips on a DG in test mode?
Low lube oil pressure 30 psig
Low turbocharger oil pressure 30 psig
High crankcase pressure 0.5 psig
What is the design bases for the DG?
Loaded onto the bus in 10 seconds
7 days of fuel
If blackout in one unit, other unit DG can provide safe shutdown power for 4 hours
When do Fuel Oil XFR pumps starts?
Both start when DG >280 rpm
One starts when low tank level 14” above centerline
What will trip DG output breaker on UV start?
F Loss of field U Underfrequency R Reverse Power N neutral overcurrent D Gen Diff current Overcurrent relay S SAT feed BRKR lockout E Stop PB
What will trip the DG output breaker on an SI start?
Differential current
Manual
After a DG start when does the CV pump sequence on?
0 seconds
Where are the DG sequencers powered from?
SARA DC 111
SARB DC 112
A sequencer timer AC 111
B sequencer timer AC 114
What are the DG ratings?
Continuous 5500 KW 954A
2000 hours 5935KW 1030A
2/24 6050KW 1050A
What is the difference between droop and isochronous mode on DG?
In iso mode governor maintains speed constant regardless of load
In droop speed lowers as load rises
After a DG start when does the SI pump sequence on?
5 seconds assuming there was an SI signal
After a DG start, when does the RH pump start?
10 seconds assuming there was a SI signal
After a DG start, when does the VC chiller sequence on?
15 seconds