Volume 7: Chapter 3, Section 12 Flashcards

1
Q

Regional Units of the ______shall issue all commercial for LPG gas less than _____ gal

A
  • Fire Prevention Division

* 1200

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

__________ of the Fire Prevention Division shall issue all permits for LPG containers more than _______ gal

A
  • Petroleum and Chemical

* 1200

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Copys of LPG permits shall be sent to _____ and _____

A
  • Petroleum and Chemical Unit of Fire Prevention Unit

* jurisdictional station

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

All LPG tanks over _____ gal shall have painted on two sides____

A
  • 60

* “Danger Flammable Liquid” and “No Smoking”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Warning signs on LPG tanks shall be ______ lettering on a ______ background

A
  • red

* white

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Warning signs on LPG tanks shall have red lettering _____ high and _____ wide

A

3” and ½ in stroke

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Gard posts around LPG must be no less than ___ in diameter or ______ if heavy trucks anticipated

A
  • 4”

* 6”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Gard posts around LPG must be no less than ______ ft above ground level

A

blank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Gard posts around LPG must be no less than ______ ft between posts

A

4 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Gard posts around LPG must be no less than _____ ft from tanks

A

5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

In a residential unit, storage of containers shall be limited to those with _____ to ______ lbs

A

2.7 - 5.0

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Piping from LPG must be able to have a working pressure of_____

A

400psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Filling connections for tanks shall be not less than _____ from any openings or entrances to buildings

A

15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Weeds, grass, brush, combustible materials shall not be _______ft from LPG containers

A

10 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

For commercial buildings not frequented by the public, LPG tanks in cannot exceed ______ water capacity

A

735

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

For commercial buildings frequented by the public LPG tanks cannot exceed _______ or ______

A

200 lbs or 2.7 lns water capacity

17
Q

LPG tanks stored outside buildings shall be located ____ ft from the egress door (if there is 1 door) or ______ if there are 2 doors

A
  • 5 ft

* 10 ft

18
Q

LPG exchange cabinets shall be at least _____ ft from any automotive service station fuel dispenser:

A

20 ft

19
Q

For LPG liquid transfer operations with ______ or more gal or more, emergency shut off shall be between ____ and _____ from the liquid transfer point

A
  • 4000
  • 25
  • 100