What two things are required to make 500 kv OPERABLE?
A
- 500 kv connected to grid by one of three lines (golden triangle)
- switchyard voltage > 512 kv
2
Q
OP J-2:VIII
Describe power limits during 500 kv line outages:
one line out?
two lines out?
A
one line out (SPS out of service)
- Voltages 24.375 to < 25 kv ==> 1800 MW
- Voltages > 25 kv ===> 2000 MW
one line out (SPS in service)
- no limitations
Two lines out (SPS irrellevant)
- 1600 MW
3
Q
OP J-2:VIII
What makes 230 kv INOPERABLE?
A
LTC in manual
52 VU 11 closed (SU bus x-tie)
voltages not in accordance with table