L-1 Flashcards

1
Q

What temperature of RCS should one RCP always be running?

Why?

A

160 deg F

ensures uniform temperture distribution

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In Modes 4 (350-200 deg) and 5 (<200 deg) what is the required position of 8701 and 8702?

why?

A

at least one breaker must be closed

allows valves to be closed quickly if a LOCA outside of containment occurs

also allows isolation if pressure rises quickly that could damage RHR system????

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When starting the first RCP for heatup what limitations apply?

Why?

A

When - Tc < 273 deg F the an RCP must not be started unless:

  • Lpzr < 50% OR
  • T s/g < 50 deg above each Tc

the concern is having an cold overpressurization condition caused by a heatup with no surge volume (273 = cold, high Lpzr = no surge volume, T s/g a lot higher than RCS = when RCP starts S/G heats up RCS and causes RCS to expand)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Per OP L-1, Before withdrawing SD banks what should/ shall be accomplished?

A

all four RCP’s should be in service

Tavg shall be above 541 deg F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly