L-3 Flashcards

1
Q

What is the minimum temperature for criticality?

What are the basis for this temperture?

What must be done if you recieve the Tave/Tref deviation alarm?

A

541 deg F

  • MTC in analyzed range (not to positive)
  • instrumentation in analyzed range
  • Pzr operable with bubble
  • RV above minimum Nil Ductility temperature

log Tavg every 30 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What must be done if you change power >15% in one hour?

Why

A

notifiy chemistry

they have requirement to sample for radioiodine spiking (checking for leaky fuel)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Why is it important to monitor Steam header pressure during ramps to 20% power?

A
  • Stm header pressure at 0% power = 1005#
  • atm dumps setpoint = 1020#
  • you are only 15# away from poping 10% stm dumps

therefore

when ramping at low powers you must monitor stm header pressure and take action if you approach setpoint

if stm dumps pop, could c/d to 541 deg F

could also cause SG feed and level transients resulting in trip and SI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Why is it important to monitor excore instrumentation during power accension to 30%?

A

low leakage cores have problems with calibration of excore detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Why should all operations that affect RCS temperature (during OP L-3) be done slowly?

A

so doppler can counter MTC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly