L-7

When aligning condensate system after a Rx trip what must you do before you start a booster pump if none are running?

Why?

A

ensure the cond. system is cooled down

using NOP place booster pump set in service

“restarting the condensate system when hot may result in significant water hammer”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

L-7

When in Mode 3 and Rod Control is capable of withdrawing rods, how many RCPs must be in operation?

rod control not capable of rod withdrawl?

A

2, capable

1, not capable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

L-7

What must be done if MSIVs are shut concerning TDAFW?

A

steam traps upstream of MSIVs (lead 2 and 3) must be placed in service or the TDAFW pmp must be declared inoperable and stm isolation valves closed (FCV-37 & 38)