what is the equation for determining maximum Lift
2nd 379
1.13 x Hg
net pump discharge pressure takes what factors into account
2nd 381
Friction loss
pump discharge pressure
intake pressure correction
what is the equation for determining pressure correction
2nd 381
Lift x total intake hose friction loss
————————————————-
2.3
what is the equation for determining net pump discharge pressure at draft
2nd 381
PDP + intake pressure correction
what is the equation for determining the adequacy of a small stream
2nd 383
AxVx7.5
The rule of thumb for evaluating a pond or small lake capacity is that for every foot of depth for an area of 1 acre provides how many GPM for how many hours
2nd 384
1000 gpm
5 hours
Floating strainers allow for drafting in water as shallow as how many feet
2nd 386
1’
which man-made static water supply source or underground storage receptacles that are usually found in areas not serviced by a hydrant system
2nd 389
cistern
which man-made static water supply source or man-made impoundments that have the same characteristics as a pond or small lake
2nd 390
ground resevoir
which man-made water supply source commonly found on large residential industrial and agricultural properties
2nd 389
Private water storage tanks
which man-made static water supply source transports water through open canals or portable pipes
2nd 391
Agricultural irrigation systems
what is the equation for determining the capacity of a square or rectangular pool
2nd 391
LxWxDx7.5
what is the equation for determining the capacity of a round pool
2nd 391
3.14 x r^2 x d x 7.5
define lift
3rd 403
Difference in elevation between the surface of the static water supply in the center of the pump intake
define theoretical lift
3rd 404
a column of water may be lifted by atmospheric pressure in a true volume at sea level height equal to 33.9 feet