Hose Testing SOG Flashcards
What is used to assign hose testing duties across shifts?
Assignments made by the person in charge of the Area of Responsibility for Hose
What is the purpose of the Hose Testing Form?
To log annual hose testing data in the Record Management System (RMS)
How is new fire hose numbered?
By year placed in service and section number (e.g., 19-10 = 2019, 10th section)
What information is recorded for each hose?
Diameter, length, hose number, and date tested
What tool is used for all fire hose testing?
Electric hose tester
Can a fire apparatus be used for hose testing?
No, use of fire apparatus for hose testing is prohibited
What PPE must be used during hose testing?
Appropriate PPE consistent with hose line operations
How often must in-service fire hose be tested?
Annually
What must be done with new hose before service?
Tested, numbered, inventoried, and documented
How long is a manufacturer’s initial service test valid?
One year or until the next OIAFR annual test
What form is used to record test results?
Hose Testing Form in the RMS (SharePoint location)
How many feet of hose can be tested per discharge?
Maximum of 300 feet
Where must hose be marked before testing?
At each coupling shank
What must be done before applying test pressure?
Ensure hose is straight and all air is bled out
What pressure and time is required to test 1¾” and 3” hose?
300 psi for 3 minutes
What pressure and time is required to test 4” and 5” hose?
200 psi for 3 minutes
What should be checked during the test?
Hose for defects and couplings for leakage
What is done after the 3-minute test is complete?
Reduce pressure to zero, close discharge, open nozzles to drain
How is failed hose handled?
Rolled in reverse with male coupling out, labeled OOS, and recorded
Who is responsible for emailing completed Hose Testing Forms?
Person in charge of the Area of Responsibility for Hose
What inspection is done after testing?
Check for cleanliness, gaskets, cuts, abrasions, and wear
How should dirty hose be cleaned?
With mild soap and water
What is done with hose after drying?
Rotated on apparatus to change storage fold position
Who reports equipment or hose failures?
The person in charge or designated liaison
Who ensures all hose is tested or rotated in time?
District Chief on each shift