1
Q

What is used to assign hose testing duties across shifts?

A

Assignments made by the person in charge of the Area of Responsibility for Hose

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of the Hose Testing Form?

A

To log annual hose testing data in the Record Management System (RMS)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How is new fire hose numbered?

A

By year placed in service and section number (e.g., 19-10 = 2019, 10th section)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What information is recorded for each hose?

A

Diameter, length, hose number, and date tested

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What tool is used for all fire hose testing?

A

Electric hose tester

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Can a fire apparatus be used for hose testing?

A

No, use of fire apparatus for hose testing is prohibited

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What PPE must be used during hose testing?

A

Appropriate PPE consistent with hose line operations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How often must in-service fire hose be tested?

A

Annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What must be done with new hose before service?

A

Tested, numbered, inventoried, and documented

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How long is a manufacturer’s initial service test valid?

A

One year or until the next OIAFR annual test

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What form is used to record test results?

A

Hose Testing Form in the RMS (SharePoint location)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How many feet of hose can be tested per discharge?

A

Maximum of 300 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where must hose be marked before testing?

A

At each coupling shank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What must be done before applying test pressure?

A

Ensure hose is straight and all air is bled out

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What pressure and time is required to test 1¾” and 3” hose?

A

300 psi for 3 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What pressure and time is required to test 4” and 5” hose?

A

200 psi for 3 minutes

17
Q

What should be checked during the test?

A

Hose for defects and couplings for leakage

18
Q

What is done after the 3-minute test is complete?

A

Reduce pressure to zero, close discharge, open nozzles to drain

19
Q

How is failed hose handled?

A

Rolled in reverse with male coupling out, labeled OOS, and recorded

20
Q

Who is responsible for emailing completed Hose Testing Forms?

A

Person in charge of the Area of Responsibility for Hose

21
Q

What inspection is done after testing?

A

Check for cleanliness, gaskets, cuts, abrasions, and wear

22
Q

How should dirty hose be cleaned?

A

With mild soap and water

23
Q

What is done with hose after drying?

A

Rotated on apparatus to change storage fold position

24
Q

Who reports equipment or hose failures?

A

The person in charge or designated liaison

25
Q

Who ensures all hose is tested or rotated in time?

A

District Chief on each shift