High Rise Buildings Flashcards

1
Q

Supplying High-Rise Standpipe System

A
  • At least 2 Engines
  • Supply at least 2 siamese
  • If only 1 siamese, supply 1st floor outlet to augment
  • ECC’s must coordinate pressures
  • Rule of thumb: Separate Engine supply system for each hand line in operation
  • Floors 1-10 = 150psi
  • Increase by 50psi every ten floors (e.g. 11-20 = 200psi, etc.)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

High Pressure Pumping

A
  • Greater than 250psi
  • Only a Chief officer can order
  • Special 3” Hi-Pressure hose must be used
  • Fittings are white and noticeably heavier
  • Connect lines to outlet opposite pump panel
  • Safety zones marked off at 50 foot intervals around working Engines, on each side of the supply line to the siamese
  • Supply line to siamese/standpipe secured w/ utility rope to substantial object
  • Unused gated inlets/outlets closed & capped
  • (2) ECC’s: 1 to pump/1 for radio communications
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

High-Pressure Engine - 3rd Stage

A

“357” 3rd stage can supply 500gpm at 700psi
(higher pressure than volume)
-Only IC (Chief Officer) can order
-May be necessary for fire above 50th floor or when water supply is unsatisfactory
-ONLY ONE 3” High-Pressure supply line into siamese may be used

How well did you know this?