Haz Mat 19/Lithium Ion Energy Storage System Flashcards

1
Q

Lithium Ion Energy Storage System..

A

-store energy to supply electrical energy at a future time

ESTOP-shut down entire system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

DON’T EVER SHUT DOWN SYSTEM without consultation..

A

UPS (uninterruptible power supply)–battery back up providing power for financial centers, shut not be shut down without consultation of building engineer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Stored/Stranded energy..

A

even after batteries are severely burned, they may still retain high voltage electrical charge (stranded energy)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

No spill hazard with these type of batteries..

A

flammable electrolyte –potentialy explosive atmosphere

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Re-ignition

A

even after final extinguishment , Li-ion-ESS may re-ginite hours to days

-may not be seen by Thermal imaging camera

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Procedures are for OUTDOOR/ROOFTOP installation …

NO FIRE/NO SMOKE SHOWING

A
  • determine if ESS battery type is Li-ion
  • establish initial danger zone
  • all FDNY personnel behind physical barriers (fence)
  • minimum 50 feet radius from containers/cabinets
  • minimum 100 feet radius from exhaust fan opening (usually located on side opposite FDC) cabinets may not have exhaust system
  • ENGINE COMPANIES secure water source, STRETCH precautionary handling , and STRETCH supply lines to supply FDC, if available (does not say charge FDC)
  • TRANSMIT 10-80 CODE 1
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

CONFIRMED FIRE/SMOKE SHOWING on arrival…

A

-determine if ESS battery is LI-ION-ESS (usually signange at FDC, if available )
-initial danger zone
-50 feet radius from container/cabinet
-100 ft radius from Exhaust opening (opposite FDC)
-SHUT DOWN ESS (ESTOP) at FDC or inside electrical room if ESS IS SUPPLYING a building
-ENGINE connect to FDC and CHARGE (signage for pressures and flow rates at the FDC)
-EXHAUSt OVERRIDE SWITCH (exhaust system)
-use exterior lines to cool adjacent cabinets and exposures if present and necessary /use narrow fog or straight stream application and maximum reach of streams
TRANSMIT 10-80 CODE 1

NOTE; IF FDC is located CLOSER than 50 feet from the nearest container , than only enter this area under the order of the IC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

POST FIRE …

A
  • may open container/cabinet doors after consultation with SME and the fire is extinguished
  • FDNY PERSONNEL NEVER ENTER CONTAINER
  • NO OVERHAULING ON ANY ESS
  • IC shall transfer responsibility to subject matter expert for decommissioning /fire watch.