EDG Auxiliaries Flashcards

1
Q

When does the EDG Crankcase Breather start?

A
  • Starts on EDG run signal
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What happens to the EDG Vent sys when outside air temp is < 45°?

A
  • tempering dampers open to stop drawing in cold outside air
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does the Tornado Damper do?

A
  • prevents a tornado from collapsing the room (act as a check valve)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

At what temp do the EDG fans start?

A
  • 95°F Room Temp
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When do the EDG Supply and Exhaust fans stop?

A
  • Stop 30 min after EDG shutdown
  • 70°F Room Temp,
    OR
  • on a CO2 actuation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How often does the gear lube oil ctrl valve open while the EDG is in stby?

A
  • Solenoid opens every 4 hours for 2 min
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When do the gear lube oil ctrl valves open when the EDG is started?

A
  • Open immediately on the start of the EDG
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When do the gear lube oil ctrl valves close after the EDG is shutdown?

A
  • 8 min after an EDG is shutdown/tripped
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What provides fuel to the EDG while its running?

A
  • The Shaft Driven Fuel Oil Pump
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When is the field flash disabled?

A
  • @ 80% speed during a fast start
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What must the Throttle Control Cylinder have to be able to open?

A
  • Ctrl Air
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How do the starting air valves fail?

A
  • As is
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When does the supply fan for the EDG Auto start?

A
  • 20 Sec after Exhaust Fan on Start of EDG

- 95°F Room Temp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When does the exhaust fan for the EDG Auto start?

A
  • Auto starts on EDG start
    or
  • 95°F Room Temp
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How much lube oil supply can the EDG Shaft Driven Pump supply?

A
  • 100% of the lube oil flow while the EDG is running
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the minimum Lvl of fuel oil in the fuel oil storage tank required for a EDG?

A

≥ 46,000 gal to supply 1 EDG for 7 days at full load per LCO 3.8.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the minimum level in the Fuel Oil Day Tank per SR 3.8.1.4?

A
  • 101.4 gal (15 minutes worth run time at full load)
18
Q

What are the designed temp bases for the EDG room?

A

< 104°F in standby

< 130°F running

19
Q

When does the Stby EDG JW Pump auto start?

A
  • starts on low # (16 psig)
20
Q

What temp does the EDG Aux Jacket Water Heater maintain the EDG Jacket Water at?

A
  • 145°F
21
Q

Unit 1 is at 100% power. A relief valve has failed open on 1AB Emergency Diesel Generator
Starting Air Receiver #1. The associated starting air compressor has tripped off.
Which one of the following correctly describes the response of 1AB Emergency Diesel
Generator if a start signal occurs before any operator action?
The EDG will …

A
  • start in the normal time from #2 Starting Air Receiver but only one starting air valve will
    supply all of the cylinders with starting air pressure.
22
Q

Upon a loss of control air, EDG air aftercooler regulating valves fail to what position?

A
  • Fails to allow full flow through the EDG air aftercooler
23
Q

What is the makeup water to the EDG JW surge tank?

A
  • Demin water
24
Q

What is the time delay for the stby JW pump on an EDG start and what is it looking for in that time frame?

A
  • 10 sec time delay if discharge # is < 16#
25
Q

What is the Emergency Backup source of water to the EDG Jacket Water Sys?

A
  • ESW
26
Q

Can the before and after pump supply the EDG while its running if the Shaft Driven oil Pump fails?

A
  • No, Before and After Pump capacity is insufficient for continued EDG operation.
27
Q

What does SR 3.8.1.6 say about an air receiver?

A
  • SR 3.8.1.6 Verify each required DG air start receiver pressure is ≥ 190# and are only good for 1 start per receiver to be considered operable
28
Q

If you have a loss of ctrl air, can you run a EDG?

A
  • No, it will not start
29
Q

How many starting air valves do you need to start a diesel?

A
  • only 1 starting air valve is needed and 1 receiver. The starting air lines and are receivers are x-tied to provide this option.
30
Q

Do both starting air valves open on a diesel start?

A
  • Yes, both valves open on a start
31
Q

What ventilation is required by T.S. L.C.O 3.8.1?

A

Both EDGs require the supply fan, the exhaust fan and the cabinet fan for an EDG to be operable or LCO 3.8.1 action statement entered.

32
Q

Will a loss of both starting air compressors prevent a start of the EDG during a LOOP?

A

No, EDG can start with both Starting air compressors out of service

33
Q

If there is a loss of 100# air what is the response from the TCC and the EDG

A

The TCC will extend closing the fuel racks and shutting down the EDG

34
Q

SV-1,2,3 are energize or de-energize to open

A

Energize to open

35
Q

What is the admin limit on the day tank volume

A

140 gallons

36
Q

With the day tank at minimum level how long will the EDG operate at full load

A

With the day tank at minimum level there will be adequate fuel to run for at least 15 minutes at full load.

The tech spec minimum level means there is 70 gallons of usable fuel oil in the tank.

37
Q

What is the cooling source for the EDG lube oil cooler

A

ESW

38
Q

How many jacket water pumps start on an EDG start (load reduction)

A

One

39
Q

When does the aux jacket water pump auto start

A

When the jacket water pumps stop

40
Q

What cools the intake air aftercoolers

A

ESW