EDG Auxiliaries Flashcards
When does the EDG Crankcase Breather start?
- Starts on EDG run signal
What happens to the EDG Vent sys when outside air temp is < 45°?
- tempering dampers open to stop drawing in cold outside air
What does the Tornado Damper do?
- prevents a tornado from collapsing the room (act as a check valve)
At what temp do the EDG fans start?
- 95°F Room Temp
When do the EDG Supply and Exhaust fans stop?
- Stop 30 min after EDG shutdown
- 70°F Room Temp,
OR - on a CO2 actuation
How often does the gear lube oil ctrl valve open while the EDG is in stby?
- Solenoid opens every 4 hours for 2 min
When do the gear lube oil ctrl valves open when the EDG is started?
- Open immediately on the start of the EDG
When do the gear lube oil ctrl valves close after the EDG is shutdown?
- 8 min after an EDG is shutdown/tripped
What provides fuel to the EDG while its running?
- The Shaft Driven Fuel Oil Pump
When is the field flash disabled?
- @ 80% speed during a fast start
What must the Throttle Control Cylinder have to be able to open?
- Ctrl Air
How do the starting air valves fail?
- As is
When does the supply fan for the EDG Auto start?
- 20 Sec after Exhaust Fan on Start of EDG
- 95°F Room Temp
When does the exhaust fan for the EDG Auto start?
- Auto starts on EDG start
or - 95°F Room Temp
How much lube oil supply can the EDG Shaft Driven Pump supply?
- 100% of the lube oil flow while the EDG is running
What is the minimum Lvl of fuel oil in the fuel oil storage tank required for a EDG?
≥ 46,000 gal to supply 1 EDG for 7 days at full load per LCO 3.8.3