Aux Building Ventilation Flashcards
What are the AES Fan Starts?
- SI
- Associated Train ECCS pump start
- CTS pump start
When is the AES Fan Charcoal bed I/S?
- Phase B (Either Train)
- Ctrl Stch in “Stop” (specific fan)
- Loss of Control Air (specific fan)
- Loss of power to either AES Fan
Where does the AES Fan take its suction from?
- CTS Heat Exchanger
- RHR Heat Exchanger
- Charging Pumps (and Reciprocating)
- SI Pump
- RHR Pump
- CTS Pump
- Fans take suction directly from Vestibule
What are the AS/AX trips?
- Load Con
- Thermal Overload
What are the AFS Trips?
- Load Con
- SFP High Rad (R-5 and VRS-5006)
- Thermal Overload
What are the AFX Trips?
- Load Con
- Charcoal Bed Fire
- Thermal Overload
When is the AFX Fan Charcoal bed I/S?
- SFP High Rad (R-5)
- SFP High Airborne Rad (VRS-5006)
- Loss of power to either fan
- Loss of control air
When do the CCW supply fans start?
- Load Con (Unit Specific)
- 1 U2 AS fan OOS 1 ACCP running
- 2 U2 AS fans OOS 2 ACCPs running
What unit are the CCW supply fans powered from?
- # 1 fan powered from Unit 2
- #2 and #3 fans powered from Unit 1
How does the CCW fans maintain temperature when its cold outside?
- Recirc damper allows for warm air to be directed from inside Aux Building during cold weather*
What does 3.7.13A (FHAEV System during fuel movement) state?
If Required FHAEV train Inoperable or not in operation
IMMEDIATELY:
- Suspend movement of irradiated fuel assemblies in the Aux Building
What will cause 12-RV-306 [Vent Stack] to Auto Trip Closed?
- A loss of BOTH Unit 1 AX Fans will close 12-RRV-306
What is the purpose of the Charcoal Filters for the Spray Add Tank Room?
- Removes radioactive iodine and methyl iodide from air
Do the Spray Add Tank Room Fans trip on a
charcoal fire?
- No, they do not
What is the 3.7.12, ESF Ventilation System Basis?
- The system limits radioactive release to within the 10 CFR 100 limits and to 5 rem TEDE for CR operators during recirc mode of a large break LOCA.