Circ Water Flashcards

1
Q

What are the CW Pump Trips?

A
  • Manual
  • Overload
  • instanteous Overcurrent
  • Undervoltage on the associated RCP Bus
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the De-icing flowpath?

A
  • From a single unit discharge vault (WMO-16 or -26), through the de-ice tunnel and out the middle intake tunnel (WMO-30 is closed).
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the indications of icing?

A
  • Circulating Water temperature ≤ 35°F.
  • 1 Foot of drawdown in the Forebay not caused by starting a CW Pump
  • Traveling screens high and/or extreme high differential pressure alarms are annunciating with little or no trash collection in the screen wash trash
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What systems support the CW System?

A
  • Chlorine Injection
  • Miscellaneous Sealing and Cooling Water
  • Screen Wash System
  • Vacuum Priming
  • 250v DC
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CW System loads?

A
  • Main Condensers
  • FP Condensers
  • TACW Hx
  • TRS Overflow
  • Radiological Liquid Waste
  • Lawn Sprinkler (Discharge Hdr)
  • Chlorine Injection (Discharge Hdr)
  • NESW (normal: intake hdr, backup: discharge hdr)
  • MSCW
Many 
Fishies
Took 
Their 
Ridiculous 
Lives 
Causing 
Needless 
Migranes
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What does T.S. 3.7.9, Ultimate Heat Sink, State?

A
  • To meet this condition, the UHS temperature limit of ≤ 86.9°F and the level should not fall below the level necessary for normal unit operation.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When do the CW outlet valves auto open?

A
  • They auto open with associated CW pump auto start to prevent pump runnout
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Will CW outlet valves auto open on a manual CW pump start?

A
  • No, you must manually open the CW outlet valves on a Manual CW Pump start. This prevents pump runout
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When do the CW outlet valves auto close?

A
  • Auto close on associated CW pump breaker opening. - Prevents short cycling the system
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When will a CW pump auto start?

A
  • With the CR Switch in Auto, the CW Pump will auto start on a failure of a running CW Pump. (Running CW control switch in Run with the breaker open.)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the CW pump power supplies?

A
  • 1D(2D) / CW Pump #11(21)
  • 1A(2A) / CW Pump #12(22)
  • 1B(2B) / CW Pump #13(23)
  • 2C / CW Pump #24
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When do the screen wash pumps auto start

A

On timer or differential level.

On a dP start the setpoint is variable and will run until dP is less than 4” for 5 seconds + 5 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

At what dP do the screens reach their maximum speed

A

25” H2O

How well did you know this?
1
Not at all
2
3
4
5
Perfectly