CHW Flashcards

1
Q

What is the purpose of the CHW system?

A
  • The system provides 55°F chilled water to containment loads (CLV, CUV, CIR, RCP MAC, S/G BD Hx)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where does the CHW head tank get its makeup water from?

A
Demin Water (normal)
NESW (alternate)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will happen if you select DISABLE on the HMI?

A

It will shutdown the entire system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the normal power supply to Unit 1 & U2 CHW System?

A

Units cross tied to transformer 10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the alternate power supply to U1 and U2 CHW system?

A

Livingston Rd

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the lower containment tech spec required bulk temperature

A

≥ 60° ≤ 120°

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the upper containment tech spec required bulk temperature

A

≥ 60° and ≤ 100°

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What pressure must be maintained according to LCO 3.6.4 (Containment Pressure)?

A

≥ -1.5# ≤ +0.3# (Modes 1-4)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does TS LCO 3.6.4 A(Containment pressure) state?

A

If containment # is not within limits:
-WITH IN 1 HR
Restore containment pressure to within limits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What’s the warmest NESW (lake temperature) the plate hx can handle and still keep chw inlet temp to cnt at 55°?

A

53°

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the CHW pump starts

A

Manual

Chiller & Pump Package Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the CHW pump trips

A

No Flow

Chiller trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the source of control power for CHW system

A

48 VDC (1 per unit) w/ battery backup

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens on a loss of CHW

A

Evaluate the system and if it cannot be restored expeditiously then start a containment pressure relief, perform swap to open loop, and disable chiller auto start.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly